Skip to main content
Siemens 3VA2563-5MN32-0JC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2563-5MN32-0JC0 Motor Protection CB, 630A, 55kA @

MPN3VA2563-5MN32-0JC0

Siemens 3VA2 series, IEC frame 1000, motor protection circuit breaker, 3-pole, 630A, ETU350M LSI trip unit, 55kA breaking capacity @ 415V AC, shunt trip 110-127V DC/AC, 2 auxiliary switches.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Product details

The Siemens 3VA2563-5MN32-0JC0 is a 3-pole motor protection circuit breaker on the IEC frame 1000 platform, rated In=630A with an ETU350M LSI trip unit. The overload protection Ir is adjustable from 250A to 630A; short-circuit protection Isd is set between 3 and 15 times Ir, and the instantaneous pickup Ii is fixed at 15 times In.

The ETU350M LSI trip unit is field-adjustable: Ir dial sets the continuous current, Isd rotary switch sets the short-time pickup multiplier, and Ii is fixed at 15x In. The shunt trip (STL) coil draws its control voltage from a 110-127V source — verify polarity for DC operation; the auxiliary switches (2x HQ) are wired to the motor control center's digital inputs for breaker status and trip indication.

Frequently asked questions

Who supplies 3VA2563-5MN32-0JC0 and how is it quoted for volume purchases?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at the time of quote.

What is the breaking capacity of this breaker at 415V?

The breaking capacity class M provides Icu=55kA at 415V AC, which is the maximum short-circuit current the breaker can safely interrupt at that voltage level.

MPN