Skip to main content
Siemens 3VA2580-5HL32-0DA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2580-5HL32-0DA0 SENTRON MCCB, 800 A, 3-Pole, ETU3

MPN3VA2580-5HL32-0DA0

Siemens SENTRON 3VA2580-5HL32-0DA0, molded case circuit breaker, 3-pole, 800 A rated continuous current (Iu), ETU320 electronic trip unit, line protection version.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2580-5HL32-0DA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2580-5HL32-0DA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C800 A
Current at 45 °C800 A
Current at 50 °C800 A
Current at 55 °C800 A
Current at 60 °C800 A
Current at 65 °C767 A
Current at 70 °C703 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 690 V53 kA
Power loss, max.135 W
3VA2580-5HL32-0DA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
3VA2580-5HL32-0DA0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2580-5HL32-0DA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
3VA2580-5HL32-0DA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2580-5HL32-0DA0 — Mechanical
ParameterValue
Height320 mm
Width210 mm
Depth120 mm
Height (in)12.6 in
Width (in)8.3 in

Product details

The Siemens SENTRON 3VA2580-5HL32-0DA0 is a 3-pole molded case circuit breaker rated for 800 A continuous current (Iu) with an ETU320 electronic trip unit, configured for line protection duty. It carries 187 kA interrupting capacity at 240 V, 121 kA at 415 V, and 53 kA at 690 V — figures that govern its selectivity and fault-clearing headroom in a distribution panel. Dimensions are 210 mm wide, 320 mm high, 120 mm deep — a standard footprint for this current class on a DIN-rail or bolted panel mount.

Thermal derating and operating envelope

The breaker holds its full 800 A rating from 40 °C through 60 °C ambient without derating. At 65 °C it must be loaded to 767 A, and at 70 °C to 703 A. Operating ambient range is -25 °C to 70 °C; storage range is -40 °C to 80 °C.

Frequently asked questions

What is the breaking capacity of 3VA2580-5HL32-0DA0 at different voltages?

At 240 V it interrupts 187 kA, at 415 V it interrupts 121 kA, and at 690 V it interrupts 53 kA. These values determine the available fault current the breaker can safely clear at each voltage level.

What trip unit does this MCCB use and what are its adjustable ranges?

It uses an ETU320 electronic trip unit. Long-time pickup Ir adjusts from 320 A to 800 A, short-time pickup Ii from 1,200 A to 8,000 A, and long-time delay tr from 0.5 to 17 seconds.

Where can I buy 3VA2580-5HL32-0DA0 and how is it quoted?

This MCCB is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at the time of quote.

What are the physical dimensions of 3VA2580-5HL32-0DA0?

Width is 210 mm, height is 320 mm, and depth is 120 mm. The front face carries IP40 protection.

MPN
3VA2580-5HL32-0DA0