Specifications

3VA2580-5HN32-0KL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2580-5HN32-0KL0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C800 A
Current at 45 °C800 A
Current at 50 °C800 A
Current at 55 °C800 A
Current at 60 °C800 A
Current at 65 °C767 A
Current at 70 °C703 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 690 V53 kA
Power loss, max.135 W
3VA2580-5HN32-0KL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
3VA2580-5HN32-0KL0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2580-5HN32-0KL0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
3VA2580-5HN32-0KL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2580-5HN32-0KL0 — Mechanical
ParameterValue
Height320 mm
Width210 mm
Depth120 mm
Height (in)12.6 in
Width (in)8.3 in

Product details

It carries an ETU350 electronic trip unit, adjustable for long-time (Ir) up to 800 A and instantaneous (Ii) up to 8000 A, giving you granular coordination with downstream feeders. Breaking capacity reaches 187 kA at 240 V, 121 kA at 415 V, and 53 kA at 690 V — figures that tell you it handles high-fault utility feeds without cascading upstream.

The 800 A rating holds flat through 60 °C ambient; at 65 °C it derates to 767 A, and at 70 °C to 703 A.

Dimensions are 320 mm high, 210 mm wide, 120 mm deep. The 120 mm depth is the key number for enclosure depth clearance — standard 400 mm deep panels clear it easily, but shallow backboxes (under 150 mm) may not. Front protection is IP40, so it's suited for indoor switchgear; no washdown rating.

Frequently asked questions

Where can I buy 3VA2580-5HN32-0KL0 and how is it quoted?

It is sourced to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer.

What is the breaking capacity of 3VA2580-5HN32-0KL0 at 415 V?

121 kA at 415 V, with 187 kA at 240 V and 53 kA at 690 V.

What trip unit does this MCCB use?

It uses an ETU350 electronic trip unit with adjustable long-time pickup (Ir) from 0.5 to 800 A and instantaneous pickup (Ii) up to 8000 A.

MPN
3VA2580-5HN32-0KL0