Siemens 3VA2580-5JP32-0AB0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2580-5JP32-0AB0 SENTRON MCCB, 800 A, 3-Pole, ETU5

MPN3VA2580-5JP32-0AB0

Siemens SENTRON 3VA2580-5JP32-0AB0, 3-pole molded case circuit breaker, 800 A rated continuous current, ETU550 electronic trip unit, line protection version.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2580-5JP32-0AB0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2580-5JP32-0AB0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C800 A
Current at 45 °C800 A
Current at 50 °C800 A
Current at 55 °C800 A
Current at 60 °C800 A
Current at 65 °C767 A
Current at 70 °C703 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 690 V53 kA
Power loss, max.135 W
3VA2580-5JP32-0AB0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550
3VA2580-5JP32-0AB0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2580-5JP32-0AB0 — Accessories & Functions
ParameterValue
Communication functionYes
Measurement functionNo
3VA2580-5JP32-0AB0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2580-5JP32-0AB0 — Mechanical
ParameterValue
Height320 mm
Width210 mm
Depth120 mm
Height (in)12.6 in
Width (in)8.3 in

Product details

800 A MCCB with ETU550 — selectivity and panel fit

The 800 A rating holds flat across the 40 °C to 60 °C ambient range — no derate needed until 65 °C (767 A) and 70 °C (703 A), which simplifies panel layout in warm enclosures. Breaking capacity runs 187 kA at 240 V, 121 kA at 415 V, and 53 kA at 690 V — numbers that put this in the high-fault tier for industrial mains distribution. The ETU550 offers adjustable long-time (Ir 0.5–1.0 x In), short-time (tsd 0.05–0.5 s), and instantaneous pickup, plus ground-fault protection is not built in (specified as 'without'). Physical footprint is 210 mm wide, 320 mm tall, 120 mm deep — a standard SENTRON 3VA frame size that fits existing 3VA panel cutouts. Front IP40 protection is adequate for enclosed switchboards; no IP rating on the rear or sides, so internal segregation within the panel matters.

The 210 mm width and 120 mm depth match the standard 3VA frame drilling pattern — drop-in compatible with existing SENTRON mounting plates and busbar systems. No rewiring needed if replacing a same-frame 3VA breaker; verify the lug kit matches the cable/ busbar termination (the order code does not include a specific lug kit, so that's a separate line item).

Frequently asked questions

Does 3VA2580-5JP32-0AB0 include ground-fault protection?

No, this version is specified 'without' ground-fault monitoring. The ETU550 trip unit supports it as an option on other order codes, but this particular variant does not include it.