Skip to main content
Siemens 3VA2580-5JP32-0HC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2580-5JP32-0HC0 SENTRON MCCB, 800 A, 3-pole, ETU5

MPN3VA2580-5JP32-0HC0

Siemens SENTRON 3VA2580-5JP32-0HC0, molded case circuit breaker, 3-pole, 800 A, ETU550 electronic trip unit, line protection version, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2580-5JP32-0HC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2580-5JP32-0HC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C800 A
Current at 45 °C800 A
Current at 50 °C800 A
Current at 55 °C800 A
Current at 60 °C800 A
Current at 65 °C767 A
Current at 70 °C703 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 690 V53 kA
Power loss, max.135 W
3VA2580-5JP32-0HC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550
3VA2580-5JP32-0HC0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2580-5JP32-0HC0 — Accessories & Functions
ParameterValue
Communication functionYes
Measurement functionNo
3VA2580-5JP32-0HC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2580-5JP32-0HC0 — Mechanical
ParameterValue
Height320 mm
Width210 mm
Depth120 mm
Height (in)12.6 in
Width (in)8.3 in

Product details

The Siemens SENTRON 3VA2580-5JP32-0HC0 is a 3-pole molded case circuit breaker (MCCB) rated for 800 A continuous current at 40 °C, with an ETU550 electronic trip unit providing adjustable long-time, short-time, and instantaneous protection — the core overcurrent release for line protection in distribution panels. Its interrupting capacity reaches 187 kA at 240 V, 121 kA at 415 V, and 53 kA at 690 V — figures that give the breaker substantial SCCR headroom for high-fault industrial services, meaning it can clear a bolted fault at those levels without cascading upstream. The frame is sized at 210 mm wide, 320 mm high, and 120 mm deep, which governs the panel cutout and bus-bar spacing required for installation.

Thermal derating and trip unit

The breaker holds its full 800 A rating from 40 °C through 60 °C ambient; above that it derates to 767 A at 65 °C and 703 A at 70 °C — a curve that matters when the MCCB is enclosed in a warm switchboard or stacked with other heat sources. The ETU550 electronic trip unit offers an adjustable long-time pickup (Ir) from 0.5 to 1.0 × In (400–800 A), a short-time delay (tsd) adjustable from 0.05 to 0.5 s, and a long-time delay (tr) from 0.5 to 25 s — enabling selective coordination with downstream breakers.

MPN
3VA2580-5JP32-0HC0