Skip to main content
Siemens 3VA2580-5KQ32-0KH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2580-5KQ32-0KH0 SENTRON MCCB, 800 A, 3-Pole, ETU8

MPN3VA2580-5KQ32-0KH0

Siemens SENTRON 3VA2580-5KQ32-0KH0, molded case circuit breaker, 3-pole, 800 A, ETU860 electronic trip unit, line protection, 187 kA at 240 V, 121 kA at 415 V, 53 kA at 690 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2580-5KQ32-0KH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2580-5KQ32-0KH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C800 A
Current at 45 °C800 A
Current at 50 °C800 A
Current at 55 °C800 A
Current at 60 °C800 A
Current at 65 °C767 A
Current at 70 °C703 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 690 V53 kA
Power loss, max.135 W
3VA2580-5KQ32-0KH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU860
3VA2580-5KQ32-0KH0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2580-5KQ32-0KH0 — Accessories & Functions
ParameterValue
Communication functionYes
Measurement functionYes
3VA2580-5KQ32-0KH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2580-5KQ32-0KH0 — Mechanical
ParameterValue
Height320 mm
Width210 mm
Depth120 mm
Height (in)12.6 in
Width (in)8.3 in

Product details

What this 800 A MCCB carries — and where the rating holds

The Siemens SENTRON 3VA2580-5KQ32-0KH0 is a 3-pole molded case circuit breaker rated for 800 A continuous current at 40 °C, with the same 800 A holding through 60 °C — only at 65 °C does it begin to derate to 767 A, and at 70 °C to 703 A. That flat thermal curve means this breaker delivers its full 800 A rating across most normal panel ambient conditions without headroom loss. Its interrupting ratings are tiered by system voltage: 187 kA at 240 V, 121 kA at 415 V, and 53 kA at 690 V. For a main breaker on a 415 V distribution board, the 121 kA SCCR gives substantial fault-clearing headroom — enough to coordinate with downstream feeders without cascading. The ETU860 electronic trip unit provides adjustable long-time pickup (Ir) up to 800 A, short-time delay (tsd) from 0.05 s to 0.5 s, and ground-fault summation sensing on the line conductors.

The breaker measures 210 mm wide, 320 mm high, and 120 mm deep — a 3-pole frame that fits standard SENTRON mounting patterns.

Frequently asked questions

Where can I buy 3VA2580-5KQ32-0KH0 and how do I get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a request for current pricing and availability.

What is 3VA2580-5KQ32-0KH0's interrupting capacity at 415 V?

121 kA at 415 V, which provides strong fault-clearing headroom for main breaker duty on a 415 V distribution board.

What trip unit does this MCCB use?

The ETU860 electronic trip unit with adjustable long-time pickup up to 800 A, short-time delay from 0.05 s to 0.5 s, and ground-fault summation sensing.

MPN