Skip to main content
Siemens 3VA2580-6HL32-0KA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2580-6HL32-0KA0 SENTRON MCCB, 800 A, 3-Pole, 242

MPN3VA2580-6HL32-0KA0

Siemens SENTRON 3VA2580-6HL32-0KA0, molded case circuit breaker, 3-pole, 800 A, ETU320 LI release, 242 kA at 240 V, 187 kA at 415 V, 74 kA at 690 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA2580-6HL32-0KA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2580-6HL32-0KA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C800 A
Current at 45 °C800 A
Current at 50 °C800 A
Current at 55 °C800 A
Current at 60 °C800 A
Current at 65 °C767 A
Current at 70 °C703 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 690 V74 kA
Power loss, max.135 W
3VA2580-6HL32-0KA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
3VA2580-6HL32-0KA0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2580-6HL32-0KA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
3VA2580-6HL32-0KA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2580-6HL32-0KA0 — Mechanical
ParameterValue
Height320 mm
Width210 mm
Depth120 mm
Height (in)12.6 in
Width (in)8.3 in

Product details

The Siemens 3VA2580-6HL32-0KA0 is a SENTRON molded case circuit breaker (MCCB) rated for 800 A continuous current at 40 °C through 60 °C, derating to 767 A at 65 °C and 703 A at 70 °C — so the full 800 A holds across typical panel ambient, and you only lose headroom above 60 °C. The 242 kA breaking capacity at 240 V and 187 kA at 415 V mean this breaker can interrupt faults up to those levels without upstream cascading; at 690 V it still clears 74 kA. That SCCR range covers most industrial service-entrance and feeder applications. The ETU320 overcurrent release provides LI (long-time and instantaneous) protection, with adjustable long-time pickup (lg) from 800 A to 8000 A and instantaneous pickup (li) from 1200 A to 8000 A — you set the trip curve to coordinate with downstream devices.

The 3VA2580-6HL32-0KA0 measures 210 mm wide, 320 mm high, and 120 mm deep — a 3-pole frame that fits standard MCCB cutouts in switchboards and panelboards.

Frequently asked questions

What is the breaking capacity of 3VA2580-6HL32-0KA0 at different voltages?

242 kA at 240 V, 187 kA at 415 V, and 74 kA at 690 V.

What overcurrent release does this MCCB use?

The ETU320 release provides LI (long-time and instantaneous) protection with adjustable pickup ranges.

Where can I buy 3VA2580-6HL32-0KA0 and how is it quoted?

It is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

MPN
3VA2580-6HL32-0KA0