Skip to main content
Siemens 3VA2580-6HN32-0AH0 — Molded Case Circuit Breakers (MCCB)

SENTRON 3VA2580-6HN32-0AH0 MCCB, 800 A, 3-Pole, ETU350

MPN3VA2580-6HN32-0AH0

SENTRON 3VA2580-6HN32-0AH0 molded case circuit breaker, 800 A, 3-pole, ETU350 electronic trip unit, line protection, IP40 front.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA2580-6HN32-0AH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2580-6HN32-0AH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C800 A
Current at 45 °C800 A
Current at 50 °C800 A
Current at 55 °C800 A
Current at 60 °C800 A
Current at 65 °C767 A
Current at 70 °C703 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 690 V74 kA
Power loss, max.135 W
3VA2580-6HN32-0AH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
3VA2580-6HN32-0AH0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2580-6HN32-0AH0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
3VA2580-6HN32-0AH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2580-6HN32-0AH0 — Mechanical
ParameterValue
Height320 mm
Width210 mm
Depth120 mm
Height (in)12.6 in
Width (in)8.3 in

Product details

The SENTRON 3VA2580-6HN32-0AH0 is a 3-pole molded case circuit breaker rated for a continuous current of 800 A, with an ETU350 electronic trip unit for adjustable overload and short-circuit protection. The 242 kA breaking capacity at 240 V and 187 kA at 415 V mean it can interrupt very high fault currents without upstream cascading — critical for main feeders and high-capacity distribution in industrial switchboards.

Trip unit and adjustability

The ETU350 electronic trip unit gives you field-adjustable long-time pickup (Ir) from 0.5 to 1.0 x In — so you can set the 800 A breaker down to 400 A if the load doesn't need the full rating. Short-time pickup (Isd) is adjustable from 1.5 to 10 x Ir, with time delays from 0.04 s to 0.4 s for selective coordination downstream. Instantaneous pickup (Ii) goes up to 10 x In (8000 A). That range lets you tune selectivity with downstream breakers without nuisance tripping.

Temperature derating and power loss

Rated at 800 A continuous from 40 °C up to 60 °C ambient — no derating needed in a warm panel. At 65 °C it drops to 767 A, and at 70 °C to 703 A.

Frequently asked questions

What is the breaking capacity of 3VA2580-6HN32-0AH0 at 415 V?

187 kA at 415 V, which covers most industrial main-feed applications.

Where can I buy the 3VA2580-6HN32-0AH0?

We source it through independent distribution and quote it to order against an RFQ — availability and current pricing are confirmed at quote time.

What are the physical dimensions of this MCCB?

Width 210 mm, height 320 mm, depth 120 mm — fits standard panel cutouts for 800 A frame breakers.

Can the 3VA2580-6HN32-0AH0 be used as a direct drop-in for a 5SQ2370-2YA04?

No evidence supports a direct mechanical or electrical drop-in between the two. The 3VA2 series uses a different frame and trip platform; verify panel cutout dimensions and bus connection layout before specifying.

MPN
3VA2580-6HN32-0AH0