Skip to main content
Siemens 3VA2580-6HN32-0BC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2580-6HN32-0BC0 SENTRON MCCB, 800 A, 242 kA at 24

MPN3VA2580-6HN32-0BC0

Siemens SENTRON 3VA2580-6HN32-0BC0, Molded case circuit breaker, 3-pole, 800 A, 242 kA at 240 V, 187 kA at 415 V, 74 kA at 690 V, ETU350 release, IP40 front, current lifecycle.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA2580-6HN32-0BC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2580-6HN32-0BC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C800 A
Current at 45 °C800 A
Current at 50 °C800 A
Current at 55 °C800 A
Current at 60 °C800 A
Current at 65 °C767 A
Current at 70 °C703 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 690 V74 kA
Power loss, max.135 W
3VA2580-6HN32-0BC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
3VA2580-6HN32-0BC0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2580-6HN32-0BC0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
3VA2580-6HN32-0BC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2580-6HN32-0BC0 — Mechanical
ParameterValue
Height320 mm
Width210 mm
Depth120 mm
Height (in)12.6 in
Width (in)8.3 in

Product details

The Siemens SENTRON 3VA2580-6HN32-0BC0 is a 3-pole molded case circuit breaker rated for 800 A continuous current, with a breaking capacity of 242 kA at 240 V, 187 kA at 415 V, and 74 kA at 690 V. It carries the ETU350 electronic trip unit, adjustable for long-time (tr) and short-time (tsd) delays, and instantaneous pickup (li) up to 8000 A. The front face is IP40 rated, suitable for panel-mount installations where splash protection is not required.

The 800 A rating holds flat from 40 °C through 60 °C, then derates to 767 A at 65 °C and 703 A at 70 °C. At 690 V it still handles 74 kA, which covers most industrial line-to-line faults on 600 V class systems.

Physical integration

Dimensions: 210 mm wide, 320 mm high, 120 mm deep. The 120 mm depth is the body depth behind the panel — verify clearance to the rear wall or bus bars.

Frequently asked questions

Where can I buy 3VA2580-6HN32-0BC0 and what is the lead time?

This part is sourced to order through independent distribution. Submit an RFQ for current availability and pricing — lead time is confirmed at quote time.

What are the key ratings of the 3VA2580-6HN32-0BC0?

It is a 3-pole MCCB rated 800 A continuous, with interrupting capacity of 242 kA at 240 V, 187 kA at 415 V, and 74 kA at 690 V. It uses an ETU350 electronic trip unit with adjustable long-time, short-time, and instantaneous settings.

What is the depth of the 3VA2580-6HN32-0BC0?

The depth is 120 mm. This is the body depth behind the panel face — ensure at least that clearance to the rear enclosure wall or bus bars.

What compliance documentation is available for this MCCB?

The part carries a reference code per DIN EN 81346-2 (Q). The manufacturer typically provides RoHS, REACH, UL, and IEC declarations — request these with your RFQ if needed for documentation packages.

MPN
3VA2580-6HN32-0BC0