Siemens 3VA2580-6HN32-0BH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2580-6HN32-0BH0 SENTRON MCCB, 800 A, 3-Pole, ETU3

MPN3VA2580-6HN32-0BH0

Siemens SENTRON 3VA2580-6HN32-0BH0, molded case circuit breaker, 3-pole, 800 A, ETU350 electronic trip unit, line protection, IP40 front.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA2580-6HN32-0BH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2580-6HN32-0BH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C800 A
Current at 45 °C800 A
Current at 50 °C800 A
Current at 55 °C800 A
Current at 60 °C800 A
Current at 65 °C767 A
Current at 70 °C703 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 690 V74 kA
Power loss, max.135 W
3VA2580-6HN32-0BH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
3VA2580-6HN32-0BH0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2580-6HN32-0BH0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
3VA2580-6HN32-0BH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2580-6HN32-0BH0 — Mechanical
ParameterValue
Height320 mm
Width210 mm
Depth120 mm
Height (in)12.6 in
Width (in)8.3 in

Product details

The Siemens 3VA2580-6HN32-0BH0 is a SENTRON molded case circuit breaker (MCCB) rated for 800 A continuous current at 40 °C, holding that rating flat through 60 °C before derating to 767 A at 65 °C and 703 A at 70 °C. That thermal profile means you can pack it into a warm enclosure — say a motor control center with several breakers side by side — without losing headroom until the ambient pushes past 65 °C. Breaking capacity is 242 kA at 240 V, 187 kA at 415 V, and 74 kA at 690 V. The 3-pole design and line-protection version mean it's built for feeder duty, not motor or generator protection. The electronic trip unit is an ETU350, which gives you adjustable long-time pickup (Ir) from 0.5 to 1.0 x In — so you can set the continuous pickup anywhere from 400 A to 800 A in steps — plus adjustable short-time (tsd 0.04–0.4 s) and instantaneous (Ii) up to 8000 A. That adjustability makes it useful for coordinating with downstream breakers in a selective scheme; you can dial in the short-time delay so a feeder fault clears before this main trips.

Panel fit and physical integration

Dimensions are 320 mm high, 210 mm wide, and 120 mm deep.

Frequently asked questions

What is the breaking capacity of this MCCB at 415 V?

At 415 V the breaking capacity is 187 kA. That's a high-interrupting rating for an 800 A frame, suitable for main feeders in industrial panels with high fault current.

What does the ETU350 trip unit allow me to adjust?

The ETU350 electronic trip unit gives you adjustable long-time pickup Ir (400–800 A), short-time delay tsd (0.04–0.4 s), and instantaneous pickup Ii (up to 8000 A). That range lets you coordinate selectivity with downstream breakers.

Where can I buy 3VA2580-6HN32-0BH0 and how is it quoted?

This part is sourced and quoted to order through independent distribution. Submit an RFQ for current pricing and availability; no stock figures or lead-time numbers are published here.

MPN
3VA2580-6HN32-0BH0