Skip to main content
Siemens 3VA2580-6HN32-0CH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2580-6HN32-0CH0 SENTRON MCCB, 800 A, 3-Pole, ETU3

MPN3VA2580-6HN32-0CH0

Siemens SENTRON 3VA2580-6HN32-0CH0, molded case circuit breaker, 3-pole, 800 A rated continuous current, ETU350 electronic trip unit, 242 kA at 240 V, 187 kA at 415 V, 74 kA at 690 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA2580-6HN32-0CH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2580-6HN32-0CH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C800 A
Current at 45 °C800 A
Current at 50 °C800 A
Current at 55 °C800 A
Current at 60 °C800 A
Current at 65 °C767 A
Current at 70 °C703 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 690 V74 kA
Power loss, max.135 W
3VA2580-6HN32-0CH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
3VA2580-6HN32-0CH0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2580-6HN32-0CH0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
3VA2580-6HN32-0CH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2580-6HN32-0CH0 — Mechanical
ParameterValue
Height320 mm
Width210 mm
Depth120 mm
Height (in)12.6 in
Width (in)8.3 in

Product details

800 A MCCB with ETU350 — interrupting capacity and thermal derating

Its interrupting capacity reaches 242 kA at 240 V, 187 kA at 415 V, and 74 kA at 690 V — figures that define the maximum fault current it can safely clear at each voltage level without upstream coordination failure. Thermal derating is flat from 40 °C through 60 °C at the full 800 A; at 65 °C the rating drops to 767 A, and at 70 °C to 703 A. This means the breaker holds its nameplate rating across most common panel ambient temperatures, but above 60 °C you must account for the reduction.

Adjustable trip settings and selectivity

The ETU350 release offers adjustable long-time pickup Ir from 0.5 to 1.0 × Iu (400 A to 800 A), with long-time delay tr adjustable from 0.5 to 17 seconds. Short-time pickup Isd and delay tsd (0.04 to 0.4 s) are also field-configurable, as is instantaneous pickup Ii up to 8000 A. These settings let the breaker be coordinated downstream for selective tripping — the short-time delay band is critical for maintaining supply to non-faulted feeders during a downstream fault.

The breaker measures 210 mm wide, 320 mm high, and 120 mm deep — a 3-pole frame that mounts into a standard switchboard or panel enclosure. The 8.3 in width and 12.6 in height help with cutout planning.

Environmental limits and power loss

MPN
3VA2580-6HN32-0CH0