Specifications

3VA2580-6HN32-0DC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2580-6HN32-0DC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C800 A
Current at 45 °C800 A
Current at 50 °C800 A
Current at 55 °C800 A
Current at 60 °C800 A
Current at 65 °C767 A
Current at 70 °C703 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 690 V74 kA
Power loss, max.135 W
3VA2580-6HN32-0DC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
3VA2580-6HN32-0DC0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2580-6HN32-0DC0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
3VA2580-6HN32-0DC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2580-6HN32-0DC0 — Mechanical
ParameterValue
Height320 mm
Width210 mm
Depth120 mm
Height (in)12.6 in
Width (in)8.3 in

Product details

The Siemens 3VA2580-6HN32-0DC0 is a SENTRON molded case circuit breaker rated for 800 A continuous current across the full 40 °C to 60 °C ambient range — no derating needed until you hit 65 °C, where it steps down to 767 A, and 703 A at 70 °C. That thermal stability makes it a solid pick for high-ambient panels near furnaces, drives, or roof-mounted gear. Breaking capacity sits at 242 kA at 240 V, 187 kA at 415 V, and 74 kA at 690 V — numbers that put it in the high-fault tier for industrial mains distribution. The 3-pole line-protection variant carries an ETU350 electronic trip unit with adjustable long-time (tr 0.5–17 s) and short-time (tsd 0.04–0.4 s) delays, plus instantaneous pickup adjustable up to 8000 A. That gives you selectivity headroom downstream without sacrificing fault clearance speed.

The 3VA2580-6HN32-0DC0 measures 320 mm high, 210 mm wide, and 120 mm deep — a standard MCCB footprint for 800 A frames. Maximum power loss is 135 W, which factors into your enclosure thermal calculation if you're stacking multiple breakers.

Frequently asked questions

What is the breaking capacity of 3VA2580-6HN32-0DC0?

242 kA at 240 V, 187 kA at 415 V, and 74 kA at 690 V — these are the interrupting ratings for this 3-pole MCCB.

How do I get pricing and availability for 3VA2580-6HN32-0DC0?

Submit an RFQ through this listing. The part is sourced to order via independent distribution; current pricing and stock are confirmed at quote time.

What trip unit does this breaker use?

It uses the ETU350 electronic overcurrent release, with adjustable long-time (tr 0.5–17 s), short-time (tsd 0.04–0.4 s), and instantaneous (li up to 8000 A) settings.

MPN
3VA2580-6HN32-0DC0