Skip to main content
Siemens 3VA2580-6HN32-0KH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2580-6HN32-0KH0 SENTRON MCCB, 800 A, 3-Pole, ETU3

MPN3VA2580-6HN32-0KH0

Siemens SENTRON 3VA2580-6HN32-0KH0, 3-pole molded case circuit breaker, 800 A rated continuous current, ETU350 electronic trip unit, line protection version.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2580-6HN32-0KH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2580-6HN32-0KH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C800 A
Current at 45 °C800 A
Current at 50 °C800 A
Current at 55 °C800 A
Current at 60 °C800 A
Current at 65 °C767 A
Current at 70 °C703 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 690 V74 kA
Power loss, max.135 W
3VA2580-6HN32-0KH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
3VA2580-6HN32-0KH0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2580-6HN32-0KH0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
3VA2580-6HN32-0KH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2580-6HN32-0KH0 — Mechanical
ParameterValue
Height320 mm
Width210 mm
Depth120 mm
Height (in)12.6 in
Width (in)8.3 in

Product details

What this 800 A MCCB brings to the panel

The Siemens 3VA2580-6HN32-0KH0 is a SENTRON molded case circuit breaker rated for 800 A continuous current across the full 40 °C to 60 °C ambient range, only beginning to derate at 65 °C (767 A) and 70 °C (703 A). That thermal stability means it holds its full rating in a warm enclosure without oversizing the frame. Breaking capacity is 242 kA at 240 V, 187 kA at 415 V, and 74 kA at 690 V — figures that put it in the high-interrupting category for large industrial services or transformer secondaries. The ETU350 electronic trip unit gives adjustable long-time (Ir 0.5–1× In, tr 0.5–17 s), short-time (Isd, tsd 0.04–0.4 s), and instantaneous (Ii up to 8000 A) protection curves, letting you coordinate downstream feeders. Front IP40, storage from -40 °C to 80 °C, operating -25 °C to 70 °C. Dimensions 320 mm high × 210 mm wide × 120 mm deep, which is a standard SENTRON 3VA frame footprint for this amp class.

Coordination and selectivity note

The ETU350's adjustable short-time delay (0.04–0.4 s) enables zone-selective interlocking with downstream breakers — useful for minimizing outage area on a fault.

Frequently asked questions

What is the breaking capacity of 3VA2580-6HN32-0KH0 at different voltages?

Breaking capacity is 242 kA at 240 V, 187 kA at 415 V, and 74 kA at 690 V.

What trip unit does this MCCB use?

It uses the ETU350 electronic trip unit with adjustable long-time, short-time, and instantaneous protection settings.

Where can I buy 3VA2580-6HN32-0KH0 and get current pricing?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ to get a firm price and lead time.

MPN
3VA2580-6HN32-0KH0