Skip to main content
Siemens 3VA2580-7HK32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2580-7HK32-0AA0 SENTRON MCCB, 800 A, 242 kA IC

MPN3VA2580-7HK32-0AA0
Active

Siemens SENTRON 3VA2580-7HK32-0AA0, molded case circuit breaker, 3-pole, 800 A, ETU340 electronic trip unit, 242 kA interrupting capacity at 415 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2580-7HK32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2580-7HK32-0AA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C800 A
Current at 45 °C800 A
Current at 50 °C800 A
Current at 55 °C800 A
Current at 60 °C800 A
Current at 65 °C767 A
Current at 70 °C703 A
Switching capacity classC
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 690 V74 kA
Power loss, max.135 W
3VA2580-7HK32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU340
3VA2580-7HK32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2580-7HK32-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Auxiliary CO contacts0
3VA2580-7HK32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-40 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2580-7HK32-0AA0 — Mechanical
ParameterValue
Height320 mm
Width210 mm
Depth120 mm
Height (in)12.6 in
Width (in)8.3 in
Depth (in)4.7 in

Product details

What this 800 A MCCB does on the line

The Siemens 3VA2580-7HK32-0AA0 is a 3-pole SENTRON molded case circuit breaker rated for a continuous current Iu of 800 A, with an interrupting capacity of 242 kA at both 240 V and 415 V — enough to handle high-fault utility feeds or large motor branch circuits without cascading upstream. It carries an ETU340 electronic trip unit with adjustable long-time pickup Ir fixed at 800 A and instantaneous pickup li fixed at 8 000 A, so the protection curve is preset for a high-current distribution or feeder application.

Dimensions are 210 mm wide by 320 mm high by 120 mm deep — a substantial frame that bolts into a distribution board or switchgear lineup, not a snap-on DIN-rail unit. Front face carries IP40 protection, so it's suited for indoor panel environments where tools or fingers won't contact live parts during normal operation.

Rated continuous current holds at 800 A from 40 °C up to 60 °C ambient; above that it derates to 767 A at 65 °C and 703 A at 70 °C. Maximum power loss is 135 W, which factors into enclosure ventilation sizing.

Frequently asked questions

Where can I buy 3VA2580-7HK32-0AA0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing — no stock count or price is published here.

What is the interrupting capacity of 3VA2580-7HK32-0AA0 at 415 V?

It interrupts 242 kA at 415 V, matching the rating at 240 V. At 690 V the capacity drops to 74 kA.

What trip unit does this MCCB use?

It uses an ETU340 electronic trip unit with fixed long-time pickup Ir at 800 A and fixed instantaneous pickup li at 8 000 A.

MPN
3VA2580-7HK32-0AA0