Skip to main content
Siemens 3VA2580-7HL42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2580-7HL42-0AA0 SENTRON MCCB, 800 A, 4-Pole, ETU3

MPN3VA2580-7HL42-0AA0
Active

Siemens SENTRON 3VA2 series, Molded case circuit breaker, 3VA2580-7HL42-0AA0, 4-pole, 800 A, ETU320 electronic trip unit, 440 kA at 240 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2580-7HL42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2580-7HL42-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C800 A
Current at 45 °C800 A
Current at 50 °C800 A
Current at 55 °C800 A
Current at 60 °C800 A
Current at 65 °C767 A
Current at 70 °C703 A
Switching capacity classC
Breaking capacity at 240 V440 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V73.5 kA
Power loss, max.231 W
3VA2580-7HL42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VA2580-7HL42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2580-7HL42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA2580-7HL42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2580-7HL42-0AA0 — Mechanical
ParameterValue
Height320 mm
Width280 mm
Depth120 mm
Height (in)12.6 in
Width (in)11.02 in
Depth (in)4.72 in

Product details

What this 800 A MCCB brings to the panel

The Siemens 3VA2580-7HL42-0AA0 is a SENTRON molded case circuit breaker (MCCB) rated for 800 A continuous current across a wide ambient range — it holds the full 800 A from 40 °C up to 60 °C, then derates to 767 A at 65 °C and 703 A at 70 °C. That flat thermal curve means you don't lose headroom in a warm enclosure unless the internal ambient pushes past 60 °C. This is a line-protection breaker (not a motor-protection or generator breaker), so the trip curves are set for feeder and distribution duty.

Breaking capacity — the real number for selectivity

At 240 V it interrupts 440 kA; at 415 V and 440 V it's 242 kA; at 500 V it's 187 kA; at 690 V it's 73.5 kA. Those are the numbers you need for arc-flash incident-energy calculations and for coordinating with upstream gear.

Dimensions: 280 mm wide, 320 mm high, 120 mm deep. That 280 mm width is the panel cutout driver — it's a wide-frame MCCB, not a compact 3VA2 frame. The trip indicator is also absent. If you need shunt trip, UVR, or comms, you add external accessories via the accessory slots — the base breaker is a straight line-protection device.

Frequently asked questions

What is the breaking capacity of 3VA2580-7HL42-0AA0 at 415 V?

242 kA at 415 V, and the same at 440 V. At 240 V it reaches 440 kA; at 690 V it's 73.5 kA.

Where can I buy 3VA2580-7HL42-0AA0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — no stock count or price is published publicly.

Will 3VA2580-7HL42-0AA0 drop into a panel specified for 3VA2110-7HK42-0AA0?

No — the 3VA2580 is an 800 A, 4-pole wide-frame MCCB (280 mm wide), while the 3VA2110 is a smaller-frame 100 A or 160 A class breaker. The panel cutout, bus spacing, and mounting hole pattern are different. They are not mechanically interchangeable without reworking the mounting plate and bus connections.

MPN
3VA2580-7HL42-0AA0