Skip to main content
Siemens 3VA2580-7HN42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2580-7HN42-0AA0 SENTRON MCCB, 800 A, 242 kA at 41

MPN3VA2580-7HN42-0AA0
Active

Siemens SENTRON 3VA2580-7HN42-0AA0, molded case circuit breaker, 4-pole, 800 A, 242 kA at 415 V, ETU350 electronic trip unit, line protection, IP40 front.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2580-7HN42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2580-7HN42-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C800 A
Current at 45 °C800 A
Current at 50 °C800 A
Current at 55 °C800 A
Current at 60 °C800 A
Current at 65 °C767 A
Current at 70 °C703 A
Switching capacity classC
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 690 V74 kA
Power loss, max.135 W
3VA2580-7HN42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
3VA2580-7HN42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2580-7HN42-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Auxiliary CO contacts0
3VA2580-7HN42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-40 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2580-7HN42-0AA0 — Mechanical
ParameterValue
Height320 mm
Width280 mm
Depth120 mm
Height (in)12.6 in
Width (in)11 in
Depth (in)4.7 in

Product details

The Siemens 3VA2580-7HN42-0AA0 is a SENTRON molded case circuit breaker rated for 800 A continuous current across the full 40 °C to 60 °C ambient range, with a 242 kA breaking capacity at both 240 V and 415 V — enough to handle high-fault utility feeds or transformer secondaries without cascading upstream. The 4-pole design with ETU350 electronic trip unit gives you adjustable long-time (tr 0.5–17 s) and short-time (tsd 0.04–0.4 s) delay bands, plus N-conductor protection configurable to OFF, 50%, or 100% of the phase setting.

The breaker holds its full 800 A rating up to 60 °C ambient. At 65 °C it derates to 767 A, and at 70 °C to 703 A — no headroom loss in a typical 40 °C panel, but worth checking if the enclosure sits near a heat source or in a non-conditioned space.

The 3VA2580-7HN42-0AA0 measures 280 mm wide by 320 mm high by 120 mm deep — a standard footprint for a 4-pole 800 A MCCB in the SENTRON 3VA platform. No DIN-rail clip — this is a bolted-frame breaker sized for bolted busbar connection.

Environmental limits

The 10 000 mechanical endurance cycles (latching) cover the expected service life for a main breaker in a distribution panel — not a daily-switched load-break device, but a protective disconnecting means.

Frequently asked questions

Where can I buy 3VA2580-7HN42-0AA0 and how do I get a price?

This part is sourced through independent distribution and quoted to order against an RFQ. Submit a request through the storefront; availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3VA2580-7HN42-0AA0 at 415 V?

The breaking capacity is 242 kA at 415 V, matching the 242 kA rating at 240 V. At 690 V it drops to 74 kA.

What trip unit does 3VA2580-7HN42-0AA0 use?

It uses the ETU350 electronic trip unit with adjustable long-time delay (tr 0.5–17 s) and short-time delay (tsd 0.04–0.4 s), plus configurable N-conductor protection (OFF, 50%, 100%).

MPN
3VA2580-7HN42-0AA0