Siemens 3VA2 series, IEC frame 1250, breaking capacity class M, Icu=55kA @ 415 V, 3-pole, line protection ETU350, LSI, In=1250A, overload protection Ir=500A...1250A, short circuit protection Isd=1.5...10 x Ir, Ii=10 x In, with undervoltage release 120-127 V AC 50/60 Hz.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Product details

The Siemens 3VA2612-5HN32-0CE0 is a 3-pole IEC frame 1250 molded case circuit breaker with a breaking capacity class M, delivering an Icu of 55 kA at 415 V AC. The rated continuous current In is 1250 A, with overload protection Ir adjustable from 500 A to 1250 A, and short-circuit protection Isd settable from 1.5 to 10 times Ir. Instantaneous pickup Ii is fixed at 10 x In. This breaker also includes an undervoltage release rated for 120–127 V AC, 50/60 Hz, mounted as an accessory inside the 3VA2 frame.

The ETU350 LSI trip unit gives you selectivity downstream: the short-time delay (Isd) lets you coordinate with downstream breakers so only the faulted branch opens, keeping the rest of the plant online. The 1250 A frame covers large feeders — think main incomers for a motor control center or a big transformer secondary. The undervoltage release trips the breaker when line voltage drops below 120–127 V AC, protecting sensitive loads from brownout conditions.

Frequently asked questions

How do I get pricing and availability for 3VA2612-5HN32-0CE0?

Submit an RFQ. This part is sourced to order through independent distribution channels; current pricing and stock levels are confirmed at quote time.

What is the breaking capacity of this breaker?

The Icu (ultimate breaking capacity) is 55 kA at 415 V AC, class M on the IEC frame 1250 platform.

What trip unit and protection functions does it have?

It uses an ETU350 electronic trip unit configured for LSI protection: long-time (overload), short-time (selective short-circuit), and instantaneous. Overload Ir is adjustable 500–1250 A, short-time Isd is 1.5–10 x Ir, and instantaneous Ii is fixed at 10 x In.