Skip to main content
Siemens 3VA4110-6ED24-1AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA4110-6ED24-1AA0 SENTRON MCCB, 100A, 2-Pole

MPN3VA4110-6ED24-1AA0
Active

Siemens SENTRON 3VA4110-6ED24-1AA0, Molded-case circuit breaker, System protection, 2-pole, 100 A, 100 kA at 240 V, TM210 release.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA4110-6ED24-1AA0 — Identification
ParameterValue
Product designationMolded-case circuit breaker
Brand / rangeSENTRON
Product versionSystem protection
3VA4110-6ED24-1AA0 — Ratings
ParameterValue
Number of poles2
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C98 A
Current at 60 °C96 A
Current at 65 °C93 A
Current at 70 °C91 A
Switching capacity classH
Breaking capacity at 240 V100 kA
Power loss, max.15.2 W
3VA4110-6ED24-1AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VA4110-6ED24-1AA0 — Construction & Connection
ParameterValue
Main circuit connection typeInfeed side: Low tab
Main circuit connector arrangementLoad side: Circular conductor terminal
Protection class (IP), frontIP40
3VA4110-6ED24-1AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA4110-6ED24-1AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA4110-6ED24-1AA0 — Mechanical
ParameterValue
Height129.4 mm
Width50.8 mm
Depth75.1 mm
Height (in)5.1 in
Width (in)2 in
Depth (in)3 in

Product details

Siemens 3VA4110-6ED24-1AA0 — SENTRON 2-Pole MCCB, 100 A Frame

The Siemens 3VA4110-6ED24-1AA0 is a 2-pole SENTRON molded-case circuit breaker (MCCB) in the System Protection product version, rated for continuous current of 100 A at 40 °C and carrying a 100 kA interrupting capacity at 240 V. It uses the TM210 thermal-magnetic overcurrent release — a fixed thermal element with adjustable magnetic trip — so the long-time pickup is fixed at 100 A, while the instantaneous magnetic trip is adjustable between 1000 A and 1000 A (fixed at 10x In for this release variant). The interrupting rating steps down with system voltage: 65 kA at 480 V, and 25 kA at 600 Y/347 V, which covers most North American 480/277 V distribution panels and 600 V class industrial feeds.

Thermal Derating and Ambient Performance

The breaker holds its full 100 A rating through 50 °C ambient, then derates linearly: 98 A at 55 °C, 96 A at 60 °C, 93 A at 65 °C, and 91 A at 70 °C — useful when the MCCB is mounted in a crowded enclosure or near heat sources. Operating ambient range is -25 °C to +70 °C, with storage from -40 °C to +80 °C; the 15.2 W maximum power loss at rated load should be factored into the enclosure thermal budget.

Dimensions are 129.4 mm high, 50.8 mm wide, and 75.1 mm deep — a 2-inch wide footprint that fits standard MCCB panel cutouts and leaves room for side-by-side mounting on a DIN rail or direct panel mount.

Frequently asked questions

Will the 3VA4110-6ED24-1AA0 drop into a panel specified for a 3VA1110-5EF32-0LA0?

The 3VA4110-6ED24-1AA0 is a 2-pole 100 A frame with a TM210 release, while the 3VA1110-5EF32-0LA0 is a different frame size and pole configuration — physical fit and wiring differ. A direct drop-in without rewiring is not expected; verify the mounting footprint and bus bar spacing before substitution.

MPN
3VA4110-6ED24-1AA0