Specifications

3VA4112-4ED34-0AA0 — Identification
ParameterValue
Product designationMolded-case circuit breaker
Brand / rangeSENTRON
3VA4112-4ED34-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Current at 40 °C125 A
Current at 45 °C12 A
Current at 50 °C120 A
Current at 55 °C117 A
Current at 60 °C115 A
Current at 65 °C112 A
Current at 70 °C109 A
Switching capacity classS
Breaking capacity at 240 V65 kA
Power loss, max.29.1 W
3VA4112-4ED34-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA4112-4ED34-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeInfeed side: Low tab
Main circuit connector arrangementoutput side: circular conductor connection
Protection class (IP), frontIP40
3VA4112-4ED34-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA4112-4ED34-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA4112-4ED34-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.15 000
Height129.4 mm
Width76.2 mm
Depth75.1 mm
Height (in)5.09 in
Width (in)3 in
Depth (in)2.96 in

Product details

The 3VA4112-4ED34-0AA0: The headline interrupting ratings tell you where this breaker can safely clear a fault: 65 kA at 240 V AC, 25 kA at 480 V AC, and 14 kA at 600 Y/347 V AC. For a 125 A frame, those numbers give substantial SCCR headroom — you can place it downstream of a transformer or a high-capacity main without worrying about cascading failure during a bolted fault. The 690 V AC rated operating voltage confirms it handles line-to-line voltages common in 400/480 V industrial networks. The 29.1 W maximum power loss matters for enclosure heat calculations, especially in a multi-breaker lineup.

At 76.2 mm wide, 129.4 mm tall, and 75.1 mm deep, this MCCB fits standard 3-pole MCCB mounting footprints in SENTRON distribution boards and third-party enclosures.

Frequently asked questions

Does this breaker include ground-fault monitoring or communication?

No. It has no ground-fault monitoring version, no undervoltage release, no communication function, and no trip indicator. It's a pure thermal-magnetic MCCB for basic overcurrent protection.