Skip to main content
Siemens 3VA4130-6ED24-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA4130-6ED24-0AA0 SENTRON MCCB, 30 A, 65 kA at 480

MPN3VA4130-6ED24-0AA0
Active

Siemens SENTRON 3VA4130-6ED24-0AA0, 2-pole molded-case circuit breaker, 30 A (40 °C), 65 kA at 480 V, TM210 release, IP40 front.

$116.84Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA4130-6ED24-0AA0 — Identification
ParameterValue
Product designationMolded-case circuit breaker
Brand / rangeSENTRON
Product versionSystem protection
3VA4130-6ED24-0AA0 — Ratings
ParameterValue
Number of poles2
Rated operational voltage Ue (AC)415 V
Current at 40 °C30 A
Current at 45 °C29 A
Current at 50 °C29 A
Current at 55 °C28 A
Current at 60 °C27 A
Current at 65 °C27 A
Current at 70 °C26 A
Switching capacity classH
Breaking capacity at 240 V100 kA
Power loss, max.6 W
3VA4130-6ED24-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VA4130-6ED24-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeInfeed side: Low tab
Protection class (IP), frontIP40
3VA4130-6ED24-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA4130-6ED24-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA4130-6ED24-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.15 000
Height129.4 mm
Width50.8 mm
Depth75.1 mm
Height (in)5.09 in
Width (in)2 in
Depth (in)2.96 in

Product details

The Siemens 3VA4130-6ED24-0AA0 is a SENTRON 2-pole molded-case circuit breaker rated 30 A at 40 °C with a TM210 thermal-magnetic release (LI characteristic). It interrupts 100 kA at 240 V and 65 kA at 480 V — enough headroom for most downstream coordination in a 480 V panel without worrying about series ratings.

Thermal derating is published all the way to 70 °C: 30 A at 40 °C drops to 26 A at 70 °C.

At 50.8 mm wide and 75.1 mm deep, this 2-pole MCCB fits a standard 50 mm DIN-rail slot.

Frequently asked questions

How do I get current pricing and availability for 3VA4130-6ED24-0AA0?

This part is sourced and quoted to order against an RFQ through independent distribution. Contact us with your quantity and target lead time for a confirmed price and delivery window.

What is 3VA4130-6ED24-0AA0's interrupting rating at 480 V?

65 kA at 480 V. It also carries 100 kA at 240 V and 25 kA at 600 Y/347 V.

What compliance documentation does this brand provide for 3VA4130-6ED24-0AA0?

The product carries a UL file designation HEAB, indicating UL 489 listing for molded-case circuit breakers. Standard RoHS and REACH declarations are available from Siemens on request.

MPN
3VA4130-6ED24-0AA0