Siemens 3VA4135-6ED14-3AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA4135-6ED14-3AA0 Circuit Breaker, 35 A, 65 kA @ 27

MPN3VA4135-6ED14-3AA0
Active

Siemens 3VA4 series, UL Frame 125, breaking capacity class H 65 kA @ 277 V, 1-pole, line protection TM210, FTFM, In=35 A, overload protection Ir=35 A permanently set, short-circuit protection Ii=10 x In.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA4135-6ED14-3AA0 — Specifications
ParameterValue
Group codeP360
Product group5385
Product classC: products manufactured / produced to order, which cannot be reused or re-utilized or be returned against credit.
SeriesOrdering Data Overview
Export control regulationsAL : N / ECCN : EAR99
Compliance with the substance restrictions according to RoHS directiveSince: 13-05-19

Product details

Circuit breaker 3VA4135-6ED14-3AA0 — key ratings and fit

The Siemens 3VA4135-6ED14-3AA0 is a 1-pole circuit breaker in the 3VA4 series, UL Frame 125, with a 35 A fixed thermal-magnetic overload release (TM210, FTFM) and a short-circuit release set to 10 x In. Breaking capacity is class H at 65 kA @ 277 V — that means it safely interrupts faults up to 65 kA at 277 V without upstream cascading, sized for high-fault panelboards and distribution boards where available short-circuit current is high. The overload protection Ir is permanently set at 35 A; the short-circuit protection Ii is fixed at 10 x In (350 A). No field-adjustable dials for Ir or Ii — the part is ordered to the exact trip setting, so verify the BOM line before committing.

RoHS compliant since 13-05-19;

Mounts on DIN rail in a standard distribution panel. The 1-pole form factor fits a single module width; the 65 kA SCCR at 277 V means it is suitable for high-fault commercial and industrial panelboards where the available fault current exceeds typical 10 kA or 25 kA ratings. Packaging dimensions 472 x 396 x 213 mm, shipped as a single piece. The part is a fixed-trip breaker — no interchangeable trip units — so the 35 A setting is locked at the factory.

Frequently asked questions

What compliance documentation does this breaker have?

RoHS compliant since 13-05-19. REACH Article 33 duty applies due to lead (CAS 7439-92-1) above 0.1% w/w. Export control is AL:N / ECCN:EAR99.

Where can I buy 3VA4135-6ED14-3AA0 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time. Because it is Product class C (made to order), order quantities should match the project — no returns or reuse.

What is the group code and product group for this part?

Group Code is P360; Product Group is 5385.

MPN
3VA4135-6ED14-3AA0