Siemens 3VA4140-4ED24-3AA0 — Molded Case Circuit Breakers (MCCB)

3VA4140-4ED24-3AA0 Siemens 3VA4 MCCB, 40 A, 25 kA @ 480 V

MPN3VA4140-4ED24-3AA0
Active

Siemens 3VA4 UL Frame 125, circuit breaker, 40 A, 25 kA @ 480 V, 2-pole, TM210, FTFM, In=40 A, overload protection Ir=40 A permanently set, short-circuit protection Ii=10 x In.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA4140-4ED24-3AA0 — Specifications
ParameterValue
Group codeP360
Product group5385
Product classC: products manufactured / produced to order, which cannot be reused or re-utilized or be returned against credit.
SeriesOrdering Data Overview
Export control regulationsAL : N / ECCN : EAR99
Compliance with the substance restrictions according to RoHS directiveSince: 13-05-19

Product details

The Siemens 3VA4140-4ED24-3AA0 is a 2-pole molded case circuit breaker from the 3VA4 series, rated 40 A continuous with a 25 kA interrupting capacity at 480 V. It uses a TM210 thermal-magnetic trip unit with fixed overload protection set at Ir=40 A and short-circuit pickup at Ii=10 x In (400 A). The UL Frame 125 designation means the breaker body is sized for 125 A frame hardware — the 40 A trip is installed at the factory, not field-interchangeable without swapping the entire unit. This is a line-protection breaker (FTFM — fixed thermal, fixed magnetic), so the Ir and Ii values are permanently set. If your load profile requires adjustable overloads or a different magnetic pickup, you need a different trip variant. The 25 kA SCCR at 480 V covers most commercial and light industrial panelboards; for higher fault currents (65 kA or 100 kA) you step up to the S or H breaking capacity class in the same 3VA4 family.

Integration notes

The 2-pole form factor occupies two module widths. Line and load lugs accept copper or aluminum conductors; torque specs are on the nameplate. The TM210 trip provides inverse-time thermal protection for overloads and instantaneous magnetic protection for shorts — coordination with downstream branch breakers requires checking the time-current curve (available in the Siemens 3VA4 selectivity manual).

Frequently asked questions

What is 3VA4140-4ED24-3AA0's interrupting rating?

25 kA at 480 V. This is the S breaking capacity class in the 3VA4 UL Frame 125 platform. For higher fault currents, use the H (65 kA) or L (100 kA) class variants in the same frame.

What compliance documentation does this breaker carry?

RoHS compliant since May 13, 2019. REACH Article 33 declares lead (CAS 7439-92-1) above 0.1% w/w. UL 489 listing is implied by the UL Frame designation. Export classification is AL N / ECCN EAR99.

Where can I buy 3VA4140-4ED24-3AA0?

This is a made-to-order product class C, so it is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.