The Siemens 3VA4145-6ED14-3AA0 is a 1-pole circuit breaker from the 3VA4 UL Frame 125 series, rated 45 A with a 65 kA interrupting capacity at 277 V. It uses a TM210 thermal-magnetic trip unit with fixed overload protection set at Ir=45 A and fixed short-circuit protection at Ii=10 x In (450 A). This is a line-protection breaker — no ground-fault or electronic trip adjustments — so the trip settings are locked at the factory. For a panel builder, that means no calibration step during commissioning, but also no field adjustment if the load changes. The 65 kA interrupting rating at 277 V puts it in the high-breaking-capacity class H, sized for service-entrance or large distribution panels where fault currents are substantial. One pole, so it's a single-phase or DC branch breaker — not a 3-phase main. Mounts in a standard panelboard or switchboard enclosure; the UL Frame 125 footprint matches the 3VA4 family's modular bus connections.
Compliance and documentation
RoHS compliant since 13-05-19. REACH Article 33 duty to inform applies: the part contains lead (CAS 7439-92-1) above 0.1% w/w in the candidate list. Export control is AL: N / ECCN: EAR99 — no special licensing required for standard industrial shipments. Packaging dimensions are 472 x 396 x 213 mm, shipped as 1 piece per unit.