Siemens 3VA4145-6ED34-3AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA4145-6ED34-3AA0 Circuit Breaker, 65 kA @ 480 V, 4

MPN3VA4145-6ED34-3AA0
Active

Siemens 3VA4 UL Frame 125, circuit breaker, 65 kA @ 480 V, 3-pole, line protection TM210, FTFM, In=45 A, overload protection Ir=45 A permanently set, short-circuit protection Ii=10 x In.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA4145-6ED34-3AA0 — Specifications
ParameterValue
Group codeP360
Product group5385
Product classC: products manufactured / produced to order, which cannot be reused or re-utilized or be returned against credit.
SeriesOrdering Data Overview
Export control regulationsAL : N / ECCN : EAR99
Compliance with the substance restrictions according to RoHS directiveSince: 13-05-19

Product details

The Siemens 3VA4145-6ED34-3AA0 is a 3-pole molded-case circuit breaker from the 3VA4 series, built on a UL Frame 125 platform. It is rated for 65 kA interrupting capacity at 480 V, placing it in the high-breaking-capacity class H. The thermal-magnetic trip unit is a TM210, with the thermal overload fixed at Ir = 45 A and the magnetic short-circuit pickup fixed at Ii = 10 × In (450 A). This is a line-protection breaker — it guards feeder and branch circuits against overload and short-circuit faults, not motor-protection duty.

RoHS compliance is confirmed since 13-05-19. Export control classifications are AL: N and ECCN: EAR99, meaning no special licensing is required for most destinations.

Packaged dimensions are 472 × 396 × 213 mm. The 3VA4 frame mounts in standard panel cutouts for UL 125 A frame breakers. Verify gland-plate clearance for the outgoing cables — the fixed thermal setting at 45 A suggests a conductor sized for 45 A continuous, but the 65 kA SCCR at 480 V means the upstream fault-current capability must be coordinated.

Frequently asked questions

Where can I buy 3VA4145-6ED34-3AA0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial response.

What compliance documentation does Siemens provide for 3VA4145-6ED34-3AA0?

RoHS compliance is documented since 13-05-19, and a REACH Article 33 duty-to-inform notification covers lead content above 0.1% w/w. Export controls are AL: N / ECCN: EAR99.

What are the key ratings of this circuit breaker?

It is a 3-pole breaker on a UL Frame 125, rated 65 kA interrupting capacity at 480 V (class H). The TM210 trip unit has a fixed thermal overload at Ir = 45 A and a fixed magnetic short-circuit pickup at Ii = 10 × In (450 A).

MPN
3VA4145-6ED34-3AA0