It interrupts 65 kA at 240 V AC and 25 kA at 480 V AC — the 65 kA figure at 240 V means it handles high available fault current on the secondary side of a typical 480/277 V step-down transformer without needing a current-limiting fuse upstream. The 690 V AC rated operating voltage covers most industrial line-to-line systems, including 600 V class in North America.
Measures 76.2 mm wide, 129.4 mm tall, and 75.1 mm deep — a standard 3-pole MCCB footprint that fits most DIN-rail or panel-mount enclosures without re-drilling.
What it does not include
This is a bare thermal-magnetic MCCB — if your application requires remote tripping or ground-fault signaling, you need the accessory version or an external relay. The TM210 release is designed for system protection (cable and busbar), not motor overload protection; for motor circuits, pair it with a separate overload relay.