Siemens 3VA4150-4ED34-3AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA4150-4ED34-3AA0 Circuit Breaker, 50 A, 25 kA @ 48

MPN3VA4150-4ED34-3AA0
Active

Siemens 3VA4 UL Frame 125 circuit breaker, class S, 25 kA @ 480 V, 3-pole, TM210 line protection, FTFM, In=50 A, Ir=50 A fixed, Ii=10 x In.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA4150-4ED34-3AA0 — Specifications
ParameterValue
Group codeP360
Product group5385
Product classC: products manufactured / produced to order, which cannot be reused or re-utilized or be returned against credit.
SeriesOrdering Data Overview
Export control regulationsAL : N / ECCN : EAR99
Compliance with the substance restrictions according to RoHS directiveSince: 13-05-19

Product details

What this breaker delivers

The Siemens 3VA4150-4ED34-3AA0 is a 3-pole molded case circuit breaker in the 3VA4 UL Frame 125 platform, rated for 50 A continuous with a fixed thermal overload setting (Ir=50 A) and a fixed short-circuit pickup of 10× In (Ii=500 A). Its interrupting rating of 25 kA at 480 V AC puts it in the 'S' (standard) breaking capacity class — enough for most downstream feeder and branch protection in North American 480Y/277 V panels, but not the high-fault 'N' or 'H' classes for transformer secondaries or service entrances. The TM210 trip unit means thermal-magnetic, non-electronic, no adjustable curves; what you see is what you get for coordination studies. This is a made-to-order unit (Product class C), not a stocked shelf item.

Integration notes

Mounts in a standard panel cutout for the 3VA4 frame. The 3-pole unit occupies the same footprint as other 125 A frame breakers in the series. Line and load lugs accept copper or aluminum conductors; torque values per the terminal marking on the breaker. No auxiliary contacts or shunt trips are included in this order code — those are ordered separately and snap into the accessory slots on the left side of the case.

Frequently asked questions

Where can I buy the 3VA4150-4ED34-3AA0 and get current pricing?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What does the TM210 trip unit mean for coordination?

The TM210 is a fixed thermal-magnetic trip: Ir is permanently set at 50 A (no adjustment dial), and the magnetic short-circuit pickup is fixed at 10× In (500 A). Coordination studies must use these fixed values — there is no electronic adjustment range to play with.

What compliance documentation is available for this breaker?

RoHS compliance is confirmed from the 2019-05-13 production date. A REACH Article 33 declaration for lead (CAS 7439-92-1) above 0.1% w/w is on file. Export control is AL: N / ECCN: EAR99.