Skip to main content
Siemens 3VA4160-4ED34-0AA0 — Molded Case Circuit Breakers (MCCB)

SENTRON 3VA4160-4ED34-0AA0 MCCB, 60 A, 65 kA at 240 V

MPN3VA4160-4ED34-0AA0
Active

SENTRON 3VA4 series molded-case circuit breaker, 3-pole, 60 A rated current Iu, 65 kA interrupting at 240 V, TM210 thermal-magnetic release, system protection version.

$102.87Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA4160-4ED34-0AA0 — Identification
ParameterValue
Product designationMolded-case circuit breaker
Brand / rangeSENTRON
Product versionSystem protection
3VA4160-4ED34-0AA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C60 A
Current at 45 °C59 A
Current at 50 °C58 A
Current at 55 °C56 A
Current at 60 °C55 A
Current at 65 °C54 A
Current at 70 °C53 A
Switching capacity classS
Breaking capacity at 240 V65 kA
Power loss, max.13.9 W
3VA4160-4ED34-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VA4160-4ED34-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeInfeed side: Low tab
Main circuit connector arrangementLoad side: Circular conductor terminal
Protection class (IP), frontIP40
3VA4160-4ED34-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA4160-4ED34-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA4160-4ED34-0AA0 — Mechanical
ParameterValue
Height129.4 mm
Width76.2 mm
Depth75.1 mm
Height (in)5.1 in
Width (in)3 in
Depth (in)3 in

Product details

The 3VA4160-4ED34-0AA0 is a 3-pole SENTRON molded-case circuit breaker rated 60 A continuous at 40 °C, with a TM210 thermal-magnetic release that trips instantaneously at 600 A (li min. and max. both set to that value). It breaks 65 kA at 240 VAC and 25 kA at 480 VAC — enough headroom for most 480 V panelboards without cascading upstream. The system protection version means it's built for feeder and main breaker duty, not just branch protection.

At 40 °C ambient it's good for 60 A; push the panel to 70 °C and the continuous rating drops to 53 A. That's a 7 A loss over 30 degrees — plan your enclosure ventilation if the breaker sits near drives or transformers. The 76.2 mm width (3 in) and 75.1 mm depth (3 in) let it land in a standard MCCB slot on a DIN rail or panel-mount base.

Power loss and thermal budget

Maximum power loss is 13.9 W at full rated current. That's modest — about the same as a small relay panel — but in a dense enclosure with multiple breakers, it adds up.

Frequently asked questions

Where can I buy 3VA4160-4ED34-0AA0?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

What are the key ratings for this MCCB?

Rated 60 A at 40 °C, 3-pole, with a TM210 thermal-magnetic release that trips instantaneously at 600 A. Interrupting capacity is 65 kA at 240 VAC and 25 kA at 480 VAC.

What compliance documentation does this breaker carry?

The product designation per UL file is SEAB, and it carries the SENTRON brand with IEC 60947-2 and UL 489 compliance. Specific RoHS/REACH declarations are available from the manufacturer.

MPN
3VA4160-4ED34-0AA0