Skip to main content
Siemens 3VA4160-4ED34-1AA0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA4160-4ED34-1AA0 MCCB, 60 A, 65 kA at 240

MPN3VA4160-4ED34-1AA0
Active

Siemens SENTRON 3VA4160-4ED34-1AA0, 3-pole molded-case circuit breaker, system protection version, 60 A rated current, 65 kA interrupting capacity at 240 V AC, TM210 thermal-magnetic release.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA4160-4ED34-1AA0 — Identification
ParameterValue
Product designationMolded-case circuit breaker
Brand / rangeSENTRON
Product versionSystem protection
3VA4160-4ED34-1AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Current at 40 °C60 A
Current at 45 °C60 A
Current at 50 °C60 A
Current at 55 °C59 A
Current at 60 °C58 A
Current at 65 °C56 A
Current at 70 °C55 A
Switching capacity classS
Breaking capacity at 240 V65 kA
Power loss, max.13.9 W
3VA4160-4ED34-1AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VA4160-4ED34-1AA0 — Construction & Connection
ParameterValue
Main circuit connection typeInfeed side: Low tab
Protection class (IP), frontIP40
3VA4160-4ED34-1AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA4160-4ED34-1AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA4160-4ED34-1AA0 — Mechanical
ParameterValue
Height129.4 mm
Width76.2 mm
Depth75.1 mm
Height (in)5.09 in
Width (in)3 in
Depth (in)2.96 in

Product details

The Siemens SENTRON 3VA4160-4ED34-1AA0 is a 3-pole molded-case circuit breaker (MCCB) in the system protection version, carrying a 60 A continuous rating at 40 °C and a 65 kA interrupting capacity at 240 V AC. That interrupting rating drops to 25 kA at 480 V AC and 14 kA at 600 Y/347 V — the numbers an engineer needs for fault-current coordination studies.

Rated current holds flat at 60 A from 40 °C through 50 °C, then begins a gradual decline: 59 A at 55 °C, 58 A at 60 °C, 56 A at 65 °C, and 55 A at 70 °C. The breaker occupies a 76.2 mm wide, 129.4 mm tall, 75.1 mm deep footprint.

UL-listed under file SEAM. Rated operating voltage is 690 V AC. Front face carries IP40 protection.

MPN
3VA4160-4ED34-1AA0