Key ratings and what they mean for your panel
The 3VA4160-6ED24-3AA0 is a 2-pole circuit breaker from the Siemens 3VA4 family on a UL Frame 125, rated for line protection with a TM210 trip unit (thermal-magnetic, fixed). The headline number here is the 65 kA interrupting capacity at 480 V — that is the fault current it can safely clear without welding contacts or rupturing the case, sized for high-fault panels where upstream coordination demands a Class H breaker. In=60 A is the continuous current rating; the overload protection Ir is permanently set at 60 A (no dial to mis-adjust), and the short-circuit pickup Ii is fixed at 10× In (600 A). For a BOM freeze, this means the breaker is not field-adjustable — what you order is what protects the branch.
Mounting and panel integration
The 3VA4 frame bolts into a standard panel or enclosure — no DIN-rail clip on this UL frame. Packaging dimensions 472×396×213 mm give an idea of the box size for shipping. Single-piece unit, no accessories included in this order code.