Skip to main content
Siemens 3VA4170-4ED24-3AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA4170-4ED24-3AA0 Circuit Breaker, 70 A, 25 kA @ 48

MPN3VA4170-4ED24-3AA0
Active

Siemens 3VA4 series, UL Frame 125 circuit breaker, 2-pole, 70 A, 25 kA @ 480 V, line protection TM210, FTFM.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA4170-4ED24-3AA0 — Specifications
ParameterValue
Group codeP360
Product group5385
Product classC: products manufactured / produced to order, which cannot be reused or re-utilized or be returned against credit.
SeriesOrdering Data Overview
Export control regulationsAL : N / ECCN : EAR99
Compliance with the substance restrictions according to RoHS directiveSince: 13-05-19

Product details

The Siemens 3VA4170-4ED24-3AA0 is a 2-pole circuit breaker from the 3VA4 series, built on a UL Frame 125 platform. It's rated for 70 A continuous (Ir fixed at 70 A) with a short-circuit breaking capacity of 25 kA at 480 V, placing it in the S (standard) breaking capacity class. The TM210 trip unit provides fixed thermal-magnetic overload protection, and the FTFM designation indicates fixed thermal, fixed magnetic settings — no field adjustment on Ir or Ii (short-circuit pickup is fixed at 10 x In). This is a line-protection breaker, sized for feeder or branch-circuit duty in a UL 489 panelboard.

The 25 kA SCCR at 480 V is the key coordination figure. For a 480 V panel with an available fault current below that threshold, this breaker is a direct fit. The fixed 70 A Ir means it's not a field-adjustable thermal — you're locked into that overload setting, so verify your continuous load is at or below 70 A (and within NEC 80% continuous-load rules for a 70 A frame). The fixed Ii at 10 x In (700 A) gives a magnetic trip threshold suitable for motor-starting inrush or high-impedance faults; if your load has a locked-rotor current above 700 A, you'll need a breaker with a higher short-circuit pickup or a different trip curve.

RoHS compliant since 13-05-19, with a REACH Article 33 duty-to-inform note for lead (CAS 7439-92-1) above 0.1% w/w.

Frequently asked questions

Where can I buy the 3VA4170-4ED24-3AA0 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing.

What is the group code and product group for this breaker?

The group code is P360 and the product group is 5385.

What compliance documentation does the 3VA4170-4ED24-3AA0 carry?

RoHS compliant since 13-05-19. REACH Article 33 duty-to-inform applies for lead (CAS 7439-92-1) above 0.1% w/w. Export control is AL: N / ECCN: EAR99.

MPN
3VA4170-4ED24-3AA0