Skip to main content
Siemens 3VA4180-4ED34-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA4180-4ED34-0AA0 SENTRON MCCB, 80 A, 65 kA at 240

MPN3VA4180-4ED34-0AA0
Active

Siemens SENTRON 3VA4180-4ED34-0AA0, 3-pole molded-case circuit breaker, 80 A at 40 °C, TM210 thermal-magnetic release, 65 kA at 240 VAC, 25 kA at 480 VAC, IP40 front, current production.

$114.30Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA4180-4ED34-0AA0 — Identification
ParameterValue
Product designationMolded-case circuit breaker
Brand / rangeSENTRON
Product versionSystem protection
3VA4180-4ED34-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Current at 40 °C80 A
Current at 45 °C78 A
Current at 50 °C77 A
Current at 55 °C75 A
Current at 60 °C74 A
Current at 65 °C72 A
Current at 70 °C70 A
Switching capacity classS
Breaking capacity at 240 V65 kA
Power loss, max.16.5 W
3VA4180-4ED34-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VA4180-4ED34-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeInfeed side: Low tab
Protection class (IP), frontIP40
3VA4180-4ED34-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA4180-4ED34-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA4180-4ED34-0AA0 — Mechanical
ParameterValue
Height129.4 mm
Width76.2 mm
Depth75.1 mm
Height (in)5.09 in
Width (in)3 in
Depth (in)2.96 in

Product details

The Siemens 3VA4180-4ED34-0AA0 is a SENTRON 3-pole molded-case circuit breaker (MCCB) rated 80 A at 40 °C ambient, with a TM210 thermal-magnetic release that provides fixed overload and short-circuit protection — no adjustable I²t curve, so it's a straight swap-in for a panel design that already calls for that trip characteristic. Breaking capacity hits 65 kA at 240 VAC and 25 kA at 480 VAC, which covers most North American 480Y/277 V distribution panels and industrial motor control centers where the available fault current is known to be under that threshold. Rated operating voltage goes to 690 VAC.

The 80 A rating holds at 40 °C; above that, the continuous current derates in 1–2 A steps per 5 °C rise, down to 70 A at 70 °C. Maximum power dissipation is 16.5 W, which is modest for an 80 A frame.

Footprint is 76.2 mm wide, 129.4 mm tall, 75.1 mm deep — a standard 3-pole MCCB form factor that drops into most SENTRON or third-party distribution blocks without panel rework. If your BOM calls for shunt trip or remote signaling, you need a different variant in the 3VA family.

UL file SEAB covers the UL 489 listing for North American installations. RoHS and REACH compliance documentation is available from Siemens for this order code.

MPN
3VA4180-4ED34-0AA0