The TM210 trip unit gives you fixed thermal-magnetic protection: overload pickup is permanently set at 80 A (Ir = 80 A), and the magnetic short-circuit pickup is fixed at 10 times In (Ii = 10 x In, so 800 A). No adjustment dials, no settings to lose — what's on the nameplate is what you get. This is a line-protection breaker, not a motor-circuit protector. The thermal element tracks the heating curve of copper conductors, so it's sized for feeder and branch-circuit protection in UL 489 applications.
RoHS compliant since May 13, 2019. Export control is straightforward — AL: N, ECCN: EAR99, so no special licensing for cross-border shipment. Packaging dimensions are 472 x 396 x 213 mm, single-piece quantity.