Skip to main content
Siemens 3VA4180-6ED14-3AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA4180-6ED14-3AA0 Circuit Breaker, 80 A, 65 kA @ 27

MPN3VA4180-6ED14-3AA0
Active

Siemens 3VA4 UL Frame 125 circuit breaker, 3VA4180-6ED14-3AA0, 1-pole, 80 A, 65 kA @ 277 V, line protection TM210, FTFM.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Specifications

3VA4180-6ED14-3AA0 — Specifications
ParameterValue
Group codeP360
Product group5385
Product classC: products manufactured / produced to order, which cannot be reused or re-utilized or be returned against credit.
SeriesOrdering Data Overview
Export control regulationsAL : N / ECCN : EAR99
Compliance with the substance restrictions according to RoHS directiveSince: 13-05-19

Product details

The Siemens 3VA4180-6ED14-3AA0 is a 1-pole molded case circuit breaker from the 3VA4 series, UL Frame 125, rated 80 A continuous. Its interrupting capacity hits 65 kA at 277 VAC — that's the H (high) breaking capacity class, meaning it clears high-fault currents without cascading upstream, which matters when you're coordinating selectivity in a panel feeding motor control centers or distribution boards.

Protection and trip unit

Fitted with a TM210 thermal-magnetic trip unit, fixed FTFM (fixed thermal, fixed magnetic). Overload protection (Ir) is permanently set at 80 A — no adjustment dial, so what you order is what protects the feeder. Short-circuit pickup (Ii) is fixed at 10 × In, or 800 A instantaneous. That's a standard motor-circuit curve; fine for general distribution and moderate inrush loads like pumps or light conveyors.

This is a Class C product — manufactured to order, not a stocked shelf item. That means lead time is tied to the production schedule, and it's non-returnable once ordered. For BOM planning, factor that into your procurement window.

RoHS compliant since 13 May 2019. Export control is straightforward — AL N / ECCN EAR99, no special licensing for most destinations.

Frequently asked questions

What is the breaking capacity of this breaker?

65 kA at 277 VAC, 1-pole. That's the H (high) breaking capacity class for the 3VA4 UL Frame 125.

What compliance documentation is available for 3VA4180-6ED14-3AA0?

RoHS compliant since 13 May 2019. REACH Article 33 duty-to-inform applies due to lead content above 0.1% w/w. Export control classification is AL N / ECCN EAR99.

Where can I buy 3VA4180-6ED14-3AA0 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time. Because it's a Class C made-to-order product, lead time depends on the production schedule.

MPN
3VA4180-6ED14-3AA0