The Siemens 3VA4195-6ED24-3AA0 is a 2-pole circuit breaker from the 3VA4 UL Frame 125 series, rated for line protection with a TM210 thermal-magnetic trip unit. Its headline rating is 65 kA interrupting capacity at 480 V — that's the fault current it can safely clear without welding contacts or rupturing the case, sized for high-fault industrial panels where a standard 25 kA breaker would arc over.
The TM210 trip is set with a fixed overload Ir of 15 A (equal to In) and a short-circuit pickup Ii of 20 × In (300 A magnetic). That means no field-adjustable dials for overload — the 15 A is locked in, which simplifies BOM consistency but means you verify the load current matches before panel build. The 2-pole construction fits standard DIN-rail or panel-mount footings in the 3VA4 family; the 65 kA SCCR at 480 V is the same across all H-class breakers in this frame.
Lifecycle status is active per the manufacturer. RoHS compliance dated from 13-05-19; REACH Article 33 declares lead (CAS 7439-92-1) above 0.1% w/w in the product. Export controls are AL: N / ECCN: EAR99 — no special license required for standard industrial shipments.