The Siemens 3VA4195-6ED34-3AA0 is a 3-pole circuit breaker from the 3VA4 series, built on a UL Frame 125 platform. It carries a 65 kA interrupting rating at 480 V (class H), sized for line protection in North American panelboards and switchgear. The TM210 trip unit is fixed at 15 A overload (Ir) with short-circuit pickup set to 20× In (Ii = 300 A).
Sourcing and compliance
Classified as product class C — manufactured or produced to order, which means it is not a stocked shelf item and cannot be reused or returned against credit. Sourcing runs through a quote-to-order process; availability and current pricing are confirmed at the time of RFQ. RoHS compliance is declared effective 13 May 2019. REACH Article 33 disclosure notes lead (CAS 7439-92-1) above 0.1% w/w in the candidate list. Export control classification is AL N / ECCN EAR99, no special license required for most destinations.
What the ratings mean for fit
The 65 kA @ 480 V SCCR is the key specification for this breaker — it tells you the device can safely interrupt a fault current up to that level without upstream coordination failure. For a 480 V distribution panel with available fault current in that range, this breaker is a direct fit. The TM210 thermal-magnetic trip provides fixed overload protection at 15 A and a magnetic short-circuit threshold of 300 A (20 × In), which is appropriate for feeder or branch circuits where the load inrush does not exceed that multiple. The UL Frame 125 form factor means it occupies the standard 3-pole mounting footprint for 125 A frame breakers. Panel builders should verify the bus-stab and lug kit compatibility with their specific panelboard, as the lug provisions are not included in this order code.