Skip to main content
Siemens 3VA9467-0GX10 — Circuit Breaker Accessories

Siemens 3VA9467-0GX10 SENTRON Aux Switch Module, 5 A, 70 mm

MPN3VA9467-0GX10
Active

Siemens SENTRON auxiliary switch module, rotary operator, 2 x leading to ON, for 3VA1 400/630 and 3VA2 100/160/250/400/630, 5 A thermal current, 70 mm depth, 88.5 mm width, 41.85 mm height.

$22.86Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA9467-0GX10 — Identification
ParameterValue
Product designationAuxiliary switch module, rotary operator
AccessoriesAuxiliary switch module
3VA9467-0GX10 — Mechanical
ParameterValue
Width88.5 mm
Height41.85 mm
Depth70 mm

Product details

The Siemens 3VA9467-0GX10 is a SENTRON auxiliary switch module with a rotary operator, designed as an accessory for 3VA molded-case circuit breakers. Rated thermal current is 5 A, and the switching capability is defined across three duty classes: AC-12 (resistive loads) at 5 A up to 240 V, AC-15 (inductive loads like contactor coils) at 2 A up to 240 V, and DC-13 (solenoid loads) at 0.2 A up to 250 V. The 0.2 A DC-13 rating is the one to watch when driving DC solenoids — the inductive break is harder on the contacts than the AC-15 figure suggests.

This module mounts into the accessory slot of 3VA1 (400/630 A frames) and 3VA2 (100/160/250/400/630 A frames) breakers. The physical envelope is 70 mm deep, 88.5 mm wide, and 41.85 mm high — a compact footprint that tucks into the breaker's side without stealing extra DIN rail space. Surge voltage resistance is 4 kV, so it holds up against switching transients on a 400 V line.

Frequently asked questions

What is the 3VA9467-0GX10 used for?

It is an auxiliary switch module for 3VA1 and 3VA2 circuit breakers, providing two contacts that signal the breaker's ON position to a control system.

Where can I buy the 3VA9467-0GX10?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What are the key ratings of the 3VA9467-0GX10?

Rated thermal current is 5 A. AC-12 switching at 5 A up to 240 V, AC-15 at 2 A up to 240 V, and DC-13 at 0.2 A up to 250 V. Surge voltage resistance is 4 kV.

Will the 3VA9467-0GX10 fit a panel designed for a 5SL4363-7?

No — the 5SL4363-7 is a 3-pole miniature circuit breaker with a different mounting footprint and function. The 3VA9467-0GX10 is an auxiliary switch module that clips onto 3VA breakers, not a direct panel drop-in.

MPN
3VA9467-0GX10