Skip to main content
Siemens 3VA9988-0BA24 — Circuit Breaker Accessories

Siemens 3VA9988-0BA24 Shunt Trip, 380-500 V AC, for 3VA

MPN3VA9988-0BA24
Active

Siemens SENTRON 3VA9988-0BA24 shunt trip (auxiliary release) for 3VA10–3VA14 and 3VA20–3VA24 molded case circuit breakers, 380–500 V AC 50/60 Hz, 650 VA maximum apparent power, compact 21.7 × 65.1 × 31.2 mm.

StockContact for availability
Lead time3-5 Days wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3VA9988-0BA24 — Identification
ParameterValue
Product designationAccessories
AccessoriesAuxiliary release

Mechanical

3VA9988-0BA24 — Mechanical
ParameterValue
Width21.7 mm
Height65.1 mm
Depth31.2 mm

Other specifications

3VA9988-0BA24 — Other specifications
ParameterValue
Number of slots3
Stripped length10 mm
Degree of pollution3
Overvoltage categoryIII
Stripped length [In]0.4 in
Design of the productauxiliary release
Surge voltage resistance4 kV
Apparent power consumption (Maximum)650 VA

Product details

The Siemens 3VA9988-0BA24 is a shunt trip (auxiliary release) accessory for the SENTRON 3VA family of molded case circuit breakers. It fits the 3VA10 through 3VA14 frames and the 3VA20 through 3VA24 frames. When energized at its rated voltage, it mechanically trips the breaker from a remote signal — a pushbutton, a safety relay, or a PLC output — without requiring an operator at the panel. The coil is rated for 380–500 V AC at 50/60 Hz, with a maximum apparent power consumption of 650 VA. That draw is the inrush to seat the trip mechanism; once the breaker opens, the coil circuit is interrupted by an internal auxiliary contact, so the control transformer or relay only sees that load momentarily.

The shunt trip measures 21.7 mm wide by 65.1 mm high by 31.2 mm deep. It mounts inside the breaker's accessory slot — no additional DIN rail space required. The three accessory slots in the 3VA frame accept this unit in one position, leaving the others free for an undervoltage release, alarm switch, or auxiliary contact block. Strip the control wires to 10 mm (0.4 in) for the screw terminals. The overvoltage category is III and the rated impulse withstand voltage is 4 kV, so the shunt trip is suitable for installation downstream of a main distribution board without additional surge suppression on the control circuit.

Frequently asked questions

What breakers does the 3VA9988-0BA24 fit?

It fits the 3VA10, 3VA11, 3VA12, 3VA13, 3VA14 frames and the 3VA20, 3VA21, 3VA22, 3VA23, 3VA24 frames.

What is the voltage rating of the 3VA9988-0BA24 shunt trip?

380–500 V AC, 50/60 Hz. Maximum apparent power consumption is 650 VA.

MPN
3VA9988-0BA24