It's specified for 48-60 V AC (50/60 Hz) or DC control circuits, drawing up to 30 VA (AC) or 30 W (DC) at maximum.
Pollution degree 3 covers conductive dust and occasional condensation, typical in industrial switchrooms. Mechanical fit is defined by the 65.1 mm height, 25.7 mm width, and 31.2 mm depth — it occupies the left accessory slot in 3VA1 and 3VA20-25 molded case breakers. The 10 mm stripped length on the control wiring matches standard ferrule preparation for the screw terminals.