The Siemens 3VM1032-3ED36-0AA2 is a 3-pole IEC frame 100 circuit breaker rated at 32 A with a breaking capacity of 25 kA at 415 V — class N, meaning it handles the standard fault levels for most industrial distribution panels without needing an upstream current-limiting device.
Mounts on DIN rail in a standard panel enclosure. The fixed thermal-magnetic trip (TM210) means the overload setting is locked at Ir=32 A — no field adjustment, so the breaker is sized exactly to the downstream load during panel design. Short-circuit protection is fixed at 10× In (320 A magnetic pickup), which coordinates with typical motor starters and feeder cables in a 415 V line.