Siemens 3VM1032-3ED32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VM1032-3ED32-0AA0 SENTRON MCCB, 3-pole 32 A TM210

MPN3VM1032-3ED32-0AA0
Active

Siemens SENTRON 3VM1032-3ED32-0AA0, 3-pole molded case circuit breaker, 32 A (40 °C), TM210 thermal-magnetic release, 76 kA at 240 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VM1032-3ED32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VM1032-3ED32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C31 A
Current at 60 °C31 A
Current at 65 °C30 A
Current at 70 °C30 A
Switching capacity classN
Breaking capacity at 240 V76 kA
Breaking capacity at 415 V53 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V8 kA
Power loss, max.11 W
3VM1032-3ED32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VM1032-3ED32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront connection
Protection class (IP), frontIP40
3VM1032-3ED32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VM1032-3ED32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VM1032-3ED32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.12 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Siemens 3VM1032-3ED32-0AA0 — 32 A SENTRON MCCB with TM210 trip unit

The Siemens 3VM1032-3ED32-0AA0 is a 3-pole SENTRON molded case circuit breaker (MCCB) rated for line protection, carrying a TM210 thermal-magnetic overcurrent release and a continuous current of 32 A at 40 °C ambient. Its interrupting capacity tracks the system voltage: 76 kA at 240 V AC, 53 kA at 415 V, 32 kA at 440 V, and 8 kA at 500 V — giving the panel designer clear SCCR headroom for common distribution voltages without oversizing the frame. That keeps the bill-of-material simple for a dedicated feeder or branch circuit where the load current is known and stable.

Panel fit and thermal derating

The breaker occupies a 76.2 mm wide by 130 mm tall footprint with a 70 mm depth — a standard 3-pole MCCB envelope that drops into most SENTRON panelboards and distribution blocks without re-spacing the DIN rail or busbar stack. Thermal derating is minimal through the 40–50 °C range (still 32 A), then drops to 31 A at 55–60 °C and 30 A at 65–70 °C. That is a gentle slope — the breaker holds its full rating across typical enclosure ambient temperatures without a frame size bump.

The wider storage window matters for unheated warehouses or job-site containers.

Frequently asked questions

What does the TM210 designation mean on this MCCB?

TM210 is a fixed thermal-magnetic overcurrent release — the '210' indicates the release class and ampere rating range. It is not adjustable; the breaker trips on a fixed thermal curve for overloads and a fixed magnetic curve for short-circuits.

MPN
3VM1032-3ED32-0AA0