Skip to main content
Siemens 3VM1050-4ED32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VM1050-4ED32-0AA0 SENTRON MCCB, 500 A, 3-Pole, TM21

MPN3VM1050-4ED32-0AA0
Active

Siemens SENTRON 3VM1050-4ED32-0AA0, molded case circuit breaker, 3-pole, 500 A frame, TM210 thermal-magnetic overcurrent release, line protection design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VM1050-4ED32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VM1050-4ED32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C50 A
Current at 45 °C50 A
Current at 50 °C50 A
Current at 55 °C49 A
Current at 60 °C48 A
Current at 65 °C46 A
Current at 70 °C45 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V76 kA
Breaking capacity at 440 V40 kA
Breaking capacity at 500 V12 kA
Power loss, max.15 W

Protection & Trip Unit

3VM1050-4ED32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VM1050-4ED32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront connection
Protection class (IP), frontIP40

Accessories & Functions

3VM1050-4ED32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0

Environmental

3VM1050-4ED32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VM1050-4ED32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.12 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

SENTRON 3VM1050-4ED32-0AA0 — 500 A MCCB with TM210 Trip

Interrupting capacity runs 121 kA at 240 V AC, dropping to 76 kA at 415 V, 40 kA at 440 V, and 12 kA at 500 V — so at 400 V class panels this breaker clears faults up to 76 kA without upstream fusing. Continuous current holds at 50 A from 40 °C through 50 °C ambient, then derates to 49 A at 55 °C, 48 A at 60 °C, 46 A at 65 °C, and 45 A at 70 °C — the thermal curve matters if the breaker sits near other heat sources in a crowded enclosure. Physical footprint: 130 mm tall, 76.2 mm wide, 70 mm deep — fits standard 3-pole MCCB panel cutouts; the IP40 front face keeps dust out of the trip mechanism in a clean indoor panel.

Panel Fit & Integration

No undervoltage release, no shunt trip, no communication module — this is a straight thermal-magnetic breaker for line protection, not a smart or remotely-tripped device. Rated insulation voltage 800 V; operating range -25 °C to 70 °C, storage from -40 °C to 80 °C. Maximum power loss 15 W at rated load — negligible for most panel thermal budgets.

Frequently asked questions

Does this breaker have a shunt trip or undervoltage release?

No — this variant has no undervoltage release, no shunt trip, and no communication function. It is a plain thermal-magnetic line-protection breaker.

MPN
3VM1050-4ED32-0AA0