Skip to main content
Siemens 3VM1050-4ED42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VM1050-4ED42-0AA0 4-Pole MCCB, 50 A, 121 kA

MPN3VM1050-4ED42-0AA0
Active

Siemens SENTRON 3VM1050-4ED42-0AA0, 4-pole molded case circuit breaker, line protection, rated 50 A continuous, TM210 thermal-magnetic release, breaking capacity 121 kA at 240 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VM1050-4ED42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VM1050-4ED42-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C50 A
Current at 45 °C50 A
Current at 50 °C50 A
Current at 55 °C49 A
Current at 60 °C48 A
Current at 65 °C46 A
Current at 70 °C45 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V76 kA
Breaking capacity at 440 V40 kA
Breaking capacity at 500 V11.9 kA
Power loss, max.14.6 W
3VM1050-4ED42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VM1050-4ED42-0AA0 — Construction & Connection
ParameterValue
Main circuit connector arrangementFront connection
Protection class (IP), frontIP40
3VM1050-4ED42-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VM1050-4ED42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VM1050-4ED42-0AA0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.1 in
Width (in)4 in
Depth (in)2.8 in

Product details

What this 4-pole MCCB covers — breaking capacity and thermal curve

Its breaking capacity is voltage-dependent: 121 kA at 240 V, 76 kA at 415 V, 40 kA at 440 V, and 11.9 kA at 500 V — meaning at 240 V it handles high-fault utility feeds, while at 500 V the lower 11.9 kA still covers most motor branch circuits. The thermal curve holds full 50 A up to 50 °C ambient; above that it derates to 49 A at 55 °C, 48 A at 60 °C, 46 A at 65 °C, and 45 A at 70 °C.

Dimensions are 70 mm deep, 101.6 mm wide, 130 mm high — a standard SENTRON 4-pole MCCB footprint that mounts directly onto a DIN rail or panel-mount base. Front-side IP40 protection means it is suitable for enclosed panels where no water ingress is expected; keep it behind a gland plate or cabinet door.

Frequently asked questions

How do I get current pricing and availability for 3VM1050-4ED42-0AA0?

Pricing and availability are confirmed at quote time against an RFQ through our independent distribution network. Submit an RFQ for a current quote and lead-time estimate.

Will 3VM1050-4ED42-0AA0 drop into a panel specified around 3VA1010-2ED32-0JA0 without rewiring?

Yes, the 3VM1050-4ED42-0AA0 is the direct functional replacement for the 3VA1010-2ED32-0JA0 — same 4-pole, 50 A, TM210 release, and similar breaking capacity. Panel footprint and wiring should be compatible for a like-for-like swap.

What is the breaking capacity of 3VM1050-4ED42-0AA0 at different voltages?

Breaking capacity is 121 kA at 240 V, 76 kA at 415 V, 40 kA at 440 V, and 11.9 kA at 500 V.

MPN
3VM1050-4ED42-0AA0