Skip to main content
Siemens 3VM1063-3ED36-0AA2 — Molded Case Circuit Breakers (MCCB)

Siemens 3VM1063-3ED36-0AA2 SENTRON MCCB, 63 A, 3-Pole, 76 kA

MPN3VM1063-3ED36-0AA2

Siemens SENTRON 3VM1063-3ED36-0AA2, molded case circuit breaker, 3-pole, 63 A (40 °C), TM210 thermal-magnetic release, 76 kA at 240 V AC, 70 mm depth, 76.2 mm width, 130 mm height.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VM1063-3ED36-0AA2 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VM1063-3ED36-0AA2 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C62 A
Current at 60 °C61 A
Current at 65 °C60 A
Current at 70 °C58 A
Switching capacity classN
Breaking capacity at 240 V76 kA
Breaking capacity at 415 V53 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V8 kA
Power loss, max.22 W
3VM1063-3ED36-0AA2 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VM1063-3ED36-0AA2 — Construction & Connection
ParameterValue
Main circuit connector arrangementFront connection
Protection class (IP), frontIP40
3VM1063-3ED36-0AA2 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VM1063-3ED36-0AA2 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VM1063-3ED36-0AA2 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Line protection MCCB — 63 A, 3-pole, TM210 release

The Siemens SENTRON 3VM1063-3ED36-0AA2 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, with a continuous current of 63 A at 40 °C and a thermal-magnetic TM210 release. It delivers a breaking capacity of 76 kA at 240 V AC, 53 kA at 415 V AC, and 32 kA at 440 V AC — figures that govern its fault-interruption capability on a given system voltage. Power loss is 22 W maximum.

Current rating holds at 63 A from 40 °C through 50 °C, then tapers: 62 A at 55 °C, 61 A at 60 °C, 60 A at 65 °C, and 58 A at 70 °C.

The 3-pole footprint fits standard panel layouts; no undervoltage release, no trip indicator, and no communication function are built in — it is a straightforward thermal-magnetic breaker for line protection duty.

Frequently asked questions

What is 3VM1063-3ED36-0AA2's listed depth?

The depth is 70 mm (2.76 in).

What is 3VM1063-3ED36-0AA2's listed width?

The width is 76.2 mm (3 in).

MPN
3VM1063-3ED36-0AA2