Siemens 3VA1063-2ED36-0DC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1063-2ED36-0DC0 SENTRON MCCB, 63 A, 3-Pole, UVR

MPN3VA1063-2ED36-0DC0

Siemens SENTRON 3VA series, Molded case circuit breaker, 3VA1063-2ED36-0DC0, 3-pole, 63 A at 40 °C, TM210 release, 32 kA at 415 V, undervoltage release fitted.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1063-2ED36-0DC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1063-2ED36-0DC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.48 A
Current at 60 °C59.22 A
Current at 65 °C57.96 A
Current at 70 °C56.7 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 690 V7.5 kA
3VA1063-2ED36-0DC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1063-2ED36-0DC0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1063-2ED36-0DC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2
3VA1063-2ED36-0DC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1063-2ED36-0DC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Rated 63 A, 3-pole MCCB with TM210 release and UVR

The Siemens SENTRON 3VA1063-2ED36-0DC0 is a 3-pole molded case circuit breaker rated 63 A continuous current at 40 °C, with the TM210 thermal-magnetic overcurrent release. That 63 A holds flat through 50 °C — only above 55 °C does it start to derate, down to 56.7 A at 70 °C ambient. The interrupting capacity hits 32 kA at 415 V, enough for most industrial distribution panels; at 240 V it reaches 52.5 kA, and at 690 V it still clears 7.5 kA. The undervoltage release (UVR) is factory-fitted, so the breaker trips if control voltage drops — typical for emergency-stop chains or mains-monitoring circuits where you need guaranteed drop-out on loss of the control supply.

Mounts on a DIN rail or panel base — the 76.2 mm width (roughly 3 x 25.2 mm per pole) and 130 mm height fit standard SENTRON 3VA cutouts. Depth is 70 mm, which leaves clearance for rear busbars and wiring ducts. Comes with 2 auxiliary switches (HQ type) pre-installed for remote status feedback.

Frequently asked questions

Where can I buy the 3VA1063-2ED36-0DC0?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

What is the interrupting rating of this MCCB at 415 V?

32 kA at 415 V. It also clears 52.5 kA at 240 V, 13.6 kA at 440 V, and 7.5 kA at 690 V.

Does this breaker include an undervoltage release?

Yes, the 3VA1063-2ED36-0DC0 ships with a factory-fitted undervoltage release (UVR) as the auxiliary release design.

MPN
3VA1063-2ED36-0DC0