Skip to main content
Siemens 3VM1080-2ED32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VM1080-2ED32-0AA0 MCCB, 80 A, 3-Pole, TM210

MPN3VM1080-2ED32-0AA0
Active

Siemens SENTRON 3VM1080-2ED32-0AA0, molded case circuit breaker, 3-pole, 80 A at 40 °C, TM210 thermal-magnetic release, 53 kA interrupting at 240 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VM1080-2ED32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VM1080-2ED32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C80 A
Current at 45 °C80 A
Current at 50 °C80 A
Current at 55 °C78 A
Current at 60 °C77 A
Current at 65 °C75 A
Current at 70 °C74 A
Switching capacity classC
Breaking capacity at 240 V53 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V14 kA
Breaking capacity at 500 V8 kA
Power loss, max.26 W
3VM1080-2ED32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VM1080-2ED32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront connection
Protection class (IP), frontIP40
3VM1080-2ED32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VM1080-2ED32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VM1080-2ED32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.12 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

It carries a 53 kA interrupting capacity at 240 V AC, dropping to 32 kA at 415 V and 8 kA at 500 V — figures that govern its fault-clearing capability at the service entrance or downstream subfeed.

TM210 release and thermal derating

The TM210 overcurrent release combines a thermal bimetal for overload protection and a magnetic coil for short-circuit response. At 40 °C, 45 °C, and 50 °C the breaker holds a full 80 A; above that it derates to 78 A at 55 °C, 77 A at 60 °C, 75 A at 65 °C, and 74 A at 70 °C.

The breaker measures 76.2 mm wide, 130 mm high, and 70 mm deep — a standard 3-pole MCCB footprint that fits most DIN-rail or panel-mount enclosures without re-drilling.

Electrical ratings and approvals context

Rated insulation voltage is 800 V, and the operating temperature range spans -25 °C to 70 °C, with storage from -40 °C to 80 °C. The breaker does not include undervoltage release, ground-fault monitoring, or communication functions — it is a straight thermal-magnetic line-protection device. No trip indicator or voltage trigger is fitted.

Frequently asked questions

Where can I buy 3VM1080-2ED32-0AA0?

This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What are the key ratings of 3VM1080-2ED32-0AA0?

80 A at 40 °C, 3-pole, TM210 thermal-magnetic release, 53 kA interrupting at 240 V, 32 kA at 415 V, 8 kA at 500 V. Rated insulation voltage 800 V. Dimensions 76.2 mm wide, 130 mm high, 70 mm deep.

Will 3VM1080-2ED32-0AA0 drop into a panel specified around 3VA1110-5ED32-0AA0?

The 3VM1080-2ED32-0AA0 is a 3-pole MCCB with a standard 76.2 mm width, so it will physically fit the same DIN-rail or panel-mount slot as the 3VA1110-5ED32-0AA0, but the 3VA series has different interrupting ratings and accessory options — verify coordination and short-circuit ratings before substituting.

MPN
3VM1080-2ED32-0AA0