Skip to main content
Siemens 3VM1080-3ED36-0AA2 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VM1080-3ED36-0AA2 MCCB, 80 A, 76 kA at 240

MPN3VM1080-3ED36-0AA2

Siemens SENTRON 3VM1080-3ED36-0AA2, molded case circuit breaker, 3-pole, 80 A continuous, breaking capacity class N, 76 kA at 240 V AC, 53 kA at 415 V AC, TM210 thermal-magnetic release, line protection.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VM1080-3ED36-0AA2 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VM1080-3ED36-0AA2 — Ratings
ParameterValue
Number of poles3
Current at 40 °C80 A
Current at 45 °C80 A
Current at 50 °C80 A
Current at 55 °C78 A
Current at 60 °C77 A
Current at 65 °C75 A
Current at 70 °C74 A
Switching capacity classN
Breaking capacity at 240 V76 kA
Breaking capacity at 415 V53 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V7.5 kA
Power loss, max.26 W
3VM1080-3ED36-0AA2 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VM1080-3ED36-0AA2 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront connection
Protection class (IP), frontIP40
3VM1080-3ED36-0AA2 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VM1080-3ED36-0AA2 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Product details

The Siemens SENTRON 3VM1080-3ED36-0AA2 is a 3-pole molded case circuit breaker (MCCB) in the 3VM frame, rated for 80 A continuous at 40 °C and carrying a breaking capacity class N — 76 kA at 240 V AC, 53 kA at 415 V AC, 32 kA at 440 V AC, and 7.5 kA at 500 V AC. The TM210 thermal-magnetic release provides fixed overload protection at Ir = 80 A and a fixed short-circuit pickup at Ii = 10 × In (800 A). This is a line-protection (LI) device, not a motor-protection breaker; it goes into distribution panels, switchboards, and feeder circuits where the load is cable or bus, not a motor starter. The box-terminal front connection suits standard panel wiring.

Above that, derate linearly: 78 A at 55 °C, 77 A at 60 °C, 75 A at 65 °C, 74 A at 70 °C. Maximum power loss is 26 W.

Frequently asked questions

What is the breaking capacity of 3VM1080-3ED36-0AA2 at 240 V and 415 V?

At 240 V AC, the interrupting rating is 76 kA. At 415 V AC, it is 53 kA. These are the Icu values for the class N breaking capacity tier.

Will 3VM1080-3ED36-0AA2 drop into a panel specified for 3VA1010-2ED42-0AE0?

Not without a selectivity review. The 3VM class N has lower interrupting capacity (53 kA vs the 3VA class S's higher rating at 415 V) and a different TM release curve. The footprint and terminal arrangement may differ — verify mechanical fit and coordination before substitution.

Where can I buy 3VM1080-3ED36-0AA2 and how is it quoted?

This part is sourced to order against an RFQ through independent industrial-automation distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer.

MPN
3VM1080-3ED36-0AA2