Siemens 3VM1010-3ED36-0AA2 — Molded Case Circuit Breakers (MCCB)

Siemens 3VM1010-3ED36-0AA2 MCCB, 100 A, 76 kA at 240 V

MPN3VM1010-3ED36-0AA2

Siemens SENTRON 3VM1010-3ED36-0AA2, molded case circuit breaker, 3-pole, 100 A, 76 kA at 240 V, TM210 release, line protection.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VM1010-3ED36-0AA2 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VM1010-3ED36-0AA2 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C98 A
Current at 60 °C96 A
Current at 65 °C94 A
Current at 70 °C91 A
Switching capacity classN
Breaking capacity at 240 V76 kA
Breaking capacity at 415 V53 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V7.5 kA
Power loss, max.39 W
3VM1010-3ED36-0AA2 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VM1010-3ED36-0AA2 — Construction & Connection
ParameterValue
Main circuit connector arrangementFront connection
Protection class (IP), frontIP40
3VM1010-3ED36-0AA2 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VM1010-3ED36-0AA2 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VM1010-3ED36-0AA2 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.1 in
Width (in)3 in
Depth (in)2.8 in

Product details

Its TM210 thermal-magnetic release (LI characteristic) provides fixed thermal pickup and magnetic trip for short-circuit protection, with no ground-fault monitoring or communication module onboard. This is a straight-ahead distribution breaker for a 3-phase panel, sized to protect a 100 A feeder.

Breaking capacity — the real-world fault rating

Breaking capacity drops sharply as line voltage rises: 76 kA at 240 V, 53 kA at 415 V, 32 kA at 440 V, and 7.5 kA at 500 V. These values are the Icu (ultimate breaking capacity) per IEC 60947-2; no Ics (service breaking capacity) is listed, so assume the standard 50% Icu for Ics unless the manual specifies otherwise.

Thermal derating — don't ignore the ambient curve

Rated 100 A up to 50 °C; above that, derate linearly: 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, 91 A at 70 °C. The TM210 release is fixed, so you cannot adjust the thermal pickup — the derating is the only way to stay within the trip curve.

Dimensions: 130 mm height, 76.2 mm width (3 inches), 70 mm depth (2.8 inches). No neutral conductor upgrade path, no motor drive accessory option. The 3-pole form factor fits standard MCCB mounting bases in distribution boards; verify the bus-bar pitch matches 76.2 mm center-to-center before committing the cutout.

Frequently asked questions

What is the closest functional second-source to 3VM1010-3ED36-0AA2?

The 3VA1010-2ED32-0JA0 is a sibling in the same SENTRON family but carries a different release and accessory set. The 3VM1010-3ED36-0AA2 uses the TM210 thermal-magnetic release with LI protection; the 3VA variant may differ in trip curve options and auxiliary contact availability. Verify the specific release and pole configuration before substituting — the 3VM is the current line-protection build.