Skip to main content
Siemens 3VM1112-5EE46-0AA2 — Molded Case Circuit Breakers (MCCB)

Siemens 3VM1112-5EE46-0AA2 Circuit Breaker, 125A, 55kA @ 415

MPN3VM1112-5EE46-0AA2

Siemens 3VM1 IEC frame 160 circuit breaker, breaking capacity class M, 4-pole, line protection TM220, ATFM, In=125A, Icu=55kA @ 415V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Product details

The Siemens 3VM1112-5EE46-0AA2 is a 4-pole IEC frame 160 circuit breaker from the 3VM1 series, rated for line protection with a TM220 thermal-magnetic trip unit. Its breaking capacity class M delivers Icu=55kA at 415 V AC, which means it can safely interrupt fault currents up to that level without upstream cascading — a key figure for panel SCCR coordination. The In=125A continuous rating with adjustable overload protection Ir=88A...125A gives you a 37 A band to dial in the exact motor or feeder load without swapping the breaker body. Short-circuit protection is fixed at Ii=10 x In (1250 A magnetic pickup), and the N conductor is unprotected — standard for a 3-phase + N installation where the neutral is not expected to carry fault current.

Mounts on DIN rail in a standard panel enclosure. The 4-pole footprint (3 poles + unprotected N) matches the common 3-phase + neutral busbar layout for IEC switchgear. Terminal connections accept copper or aluminum conductors up to the frame's rated cross-section — verify lug sizing against the 125 A continuous current for your specific wire type.

Frequently asked questions

What is the breaking capacity of the 3VM1112-5EE46-0AA2?

The ultimate breaking capacity Icu is 55 kA at 415 V AC, which is the class M rating for the 3VM1 IEC frame 160.

Where can I buy the 3VM1112-5EE46-0AA2?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What does the TM220 trip unit mean on this breaker?

TM220 indicates a thermal-magnetic trip unit with a fixed magnetic pickup at 10 x In (1250 A) and an adjustable thermal overload range of 88 A to 125 A, allowing fine-tuning for the protected load without changing the breaker.

MPN
3VM1112-5EE46-0AA2