Specifications

Identification

3VM1116-3EE36-0AA2 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VM1116-3EE36-0AA2 — Ratings
ParameterValue
Number of poles3
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C158 A
Current at 60 °C155 A
Current at 65 °C153 A
Current at 70 °C150 A
Switching capacity classN
Breaking capacity at 240 V76 kA
Breaking capacity at 415 V53 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V11.9 kA
Power loss, max.38 W

Protection & Trip Unit

3VM1116-3EE36-0AA2 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220
Overcurrent protection functionLI
Ground-fault monitoringWithout

Construction & Connection

3VM1116-3EE36-0AA2 — Construction & Connection
ParameterValue
Main circuit connector arrangementFront connection
Protection class (IP), frontIP40

Accessories & Functions

3VM1116-3EE36-0AA2 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0

Environmental

3VM1116-3EE36-0AA2 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VM1116-3EE36-0AA2 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.1 in
Width (in)3 in
Depth (in)2.8 in

Product details

What this MCCB carries — and where it stops

The Siemens 3VM1116-3EE36-0AA2 is a 3-pole SENTRON molded case circuit breaker (MCCB) rated for continuous 160 A at up to 40 °C ambient, with a TM220 thermal-magnetic trip unit — fixed thermal (160 A) and adjustable magnetic (160–1600 A). Its breaking capacity drops from 76 kA at 240 V to 53 kA at 415 V, 32 kA at 440 V, and 11.9 kA at 500 V, so the voltage at the fault point determines whether this breaker clears a high-fault event without upstream coordination. At 690 V insulation rating (Ui), it handles 500 V DC max as well. The front face carries IP40 protection — fine for a dry panel, not for washdown areas.

Thermal derating — the real current limit

Rated 160 A up to 50 °C, then it tapers: 158 A at 55 °C, 155 A at 60 °C, 153 A at 65 °C, and 150 A at 70 °C. If your panel ambient runs above 50 °C, size the load side for the derated value — the breaker won't nuisance-trip, but it won't carry the full 160 A either. Maximum power loss is 38 W, which matters for heat buildup in a compact enclosure.

Footprint and panel fit

Dimensions are 130 mm high, 76.2 mm wide, 70 mm deep — a standard 3-pole MCCB footprint that fits most DIN-rail or screw-mounted panel layouts. The IP40 front means it's intended for enclosure mounting, not exposed installation. No communication module or motor drive option on this variant; it's a straight line-protection breaker.