Skip to main content
Siemens 3VM1116-4ED32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VM1116-4ED32-0AA0 SENTRON MCCB, 160A, 3-Pole, TM210

MPN3VM1116-4ED32-0AA0
Active

Siemens SENTRON 3VM1116-4ED32-0AA0, molded case circuit breaker, 3-pole, 160 A, TM210 thermal-magnetic release, line protection, breaking capacity 121 kA at 240 V AC.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VM1116-4ED32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VM1116-4ED32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C158 A
Current at 60 °C155 A
Current at 65 °C153 A
Current at 70 °C150 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V76 kA
Breaking capacity at 440 V53 kA
Breaking capacity at 500 V12 kA
Power loss, max.38 W

Protection & Trip Unit

3VM1116-4ED32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VM1116-4ED32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront connection
Protection class (IP), frontIP40

Accessories & Functions

3VM1116-4ED32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0

Environmental

3VM1116-4ED32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VM1116-4ED32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.15 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The Siemens SENTRON 3VM1116-4ED32-0AA0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, with a TM210 thermal-magnetic overcurrent release. It carries 160 A continuously at 40 °C ambient and provides a maximum breaking capacity of 1 600 A — the 121 kA at 240 V AC is the rating that governs fault clearing on most low-voltage distribution panels.

Key ratings and what they mean for fit

Rated 160 A at 40 °C, derating to 150 A at 70 °C — the thermal curve is flat up to 50 °C, then drops by roughly 2 A per 5 °C step through 70 °C. That means in a warm enclosure (55 °C internal) you still get 158 A headroom, so a 150 A continuous load is safe without oversizing. The TM210 release combines a thermal bimetal for overload protection and a magnetic coil for short-circuit response; the '210' designator indicates the magnetic trip level, which is fixed and non-adjustable. Breaking capacity is the real selector: 121 kA at 240 V, 76 kA at 415 V, 53 kA at 440 V, and 12 kA at 500 V. On a 480 V panel (common in North America) the 440 V figure of 53 kA is the closest published rating — adequate for most industrial services with a transformer impedance-limited fault current. The 1 600 A maximum rating is the frame limit, not the continuous rating; the actual continuous current is set by the installed trip unit. Insulation voltage rated at 800 V, with IP40 protection on the front face — suitable for enclosed panel mounting where the cover provides the environmental seal. Power dissipation is 38 W maximum at rated load, which factors into enclosure thermal calculations when stacking multiple breakers.

Where it is used

This MCCB is designed for line protection — the primary feeder or branch circuit in a low-voltage distribution board, motor control center, or panelboard. It protects cables, busbars, and downstream equipment against overload and short-circuit faults. The 3-pole configuration suits three-phase systems (delta or wye, solidly grounded or impedance-grounded).

Lifecycle and sourcing

Listed as current production (active lifecycle stage). No phase-out or last-time-buy notice appears. The part is sourced to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

Physical integration

Dimensions: 130 mm height, 76.2 mm width, 70 mm depth. The 76.2 mm width (3 inches) is the standard 3-pole MCCB footprint for this frame size.

Frequently asked questions

What does the TM210 release designation mean?

TM210 is a thermal-magnetic overcurrent release. The '210' indicates the fixed magnetic short-circuit trip level; the thermal element provides inverse-time overload protection. It is non-adjustable and factory-set.

What are the operating temperature limits for this MCCB?

Operating range is -25 °C to +70 °C ambient. Storage range is -40 °C to +80 °C. Continuous current derates from 160 A at 40 °C to 150 A at 70 °C.

MPN
3VM1116-4ED32-0AA0